Siemens SIMATIC ET 200SP Manual page 46

Analog input module ai 2xu/i 2-/4-wire hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
Article number
Crosstalk between the inputs, min.
Repeat accuracy in steady state at 25 °C (rela-
tive to input range), (+/-)
Operational error limit in overall temperature
range
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Interference voltage suppression for f = n x (f1
+/- 1 %), f1 = interference frequency
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Filtering and processing time (TCI), min.
Bus cycle time (TDP), min.
Jitter, max.
Interrupts/diagnostics/status information
Diagnostics function
Alarms
Diagnostic alarm
Limit value alarm
Diagnoses
Monitoring the supply voltage
Wire-break
Short-circuit
Group error
Overflow/underflow
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
Channel status display
for channel diagnostics
for module diagnostics
Potential separation
Potential separation channels
between the channels
between the channels and backplane bus
50
6ES7134-6HB00-0CA1
-50 dB
0.01 %
0.1 %
0.1 %
0.05 %; 0.1 % at SFU 4.8 kHz
0.05 %; 0.1 % at SFU 4.8 kHz
35 V
90 dB
800 µs
1 ms
5 µs
Yes
Yes
Yes; two upper and two lower limit values in each
case
Yes
Yes; Measuring range 4 to 20 mA only
Yes; channel-by-channel, at 1 to 5 V or for short-
circuit in encoder supply
Yes
Yes
Yes; green LED
Yes; red LED
Yes; green/red DIAG LED
Yes
Yes
Analog input module AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1)
Equipment Manual, 05/21, A5E51055079-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7134-6hb00-0ca1

Table of Contents