Riello BAG3 MIX FAMILY COND Instructions For The Installer And For Technical Assistance page 36

Table of Contents

Advertisement

Available languages

Available languages

Proportional head
PP1
Curve 1
PP2
Curve 2
PP3
Curve 3
factory settings
Constant head
Curve 1
CP1
Curve 2
CP3
Curve 3
CP3
Constant curve
CC1
Speed 1
CC2
Speed 2
CC3
Speed 3
CC4
MAX speed
LED 1
LED 2
LED 3
LED 4
LED 5
green
yellow
yellow
yellow
yellow
LED 1
LED 2
LED 3
LED 4
LED 5
green
yellow
yellow
yellow
yellow
LED 1
LED 2
LED 3
LED 4
LED 5
green
yellow
yellow
yellow
yellow
Proportional head
The circulation unit works on the basis of the heat request made
by the system. The working point of the circulation unit and the
selected proportional head curve move on the basis of the heat
request
PP1
PP1
LOW proportional head curve
PP2
AVERAGE proportional head curve
PP3
HIGH proportional head curve
Constant head
The circulation unit works at constant head, irrespective of the
heat request. The working point of the circulation unit will move
along the selected curve on the basis of the heat request.
CP1
CP1
LOW constant head curve
CP2
AVERAGE constant head curve
CP3
HIGH constant head curve
Constant curve
The circulation unit works at constant speed, irrespective of the
heat request from the system. The working point of the circula-
tion unit will move along the selected curve on the basis of the
heat request.
C1
C2
C1
Curve 1 = 4 metres
C2
Curve 2 = 5 metres
C3
Curve 3 = 6 metres
C4
Curve 4 MAX = 7 metres
36
PP2
PP3
CP2
CP3
C3
C4

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20102824

Table of Contents