These records are stored in non volatile
memory. Therefore, there is no need
for internal battery monitoring or
maintenance.
Trip circuit monitoring
0XOWLOLQ XQLWV R HU DV DQ RSWLRQ WZR
complete supervision circuits for breaker
trip and closing coils and circuits. These
supervision inputs monitor both the
battery voltage level and the continuity of
the trip and/or closing circuits, applying
current through those circuits and
FKHFNLQJ WKDW LW ÀRZV SURSHUO\ ,Q RUGHU
to apply this feature it is necessary to
choose I/O board 1 option 2.
User Interface
Functional Block Diagram
52
79
1
CLOSE
TRIP
Monitoring
3
50BF
49
50PH
50PL
46
48
32FP
1
3
3
3
3
3
3
1
2
2
50G
51G
67G
3
3
3
1
50SG 51SG
50IG
67SG
3
3
3
3
3
47
27
59
VTFF
81U
81O
3
3
3
1
3
3
F650
Digital Bay Controller
Communications
0XOWLOLQ XQLWV LQFRUSRUDWH XS WR
three ports that operate independently.
Redundant ports are available for high
reliability applications:
Available protocols for rear port 1 and 2
are ModBus RTU, IEC 103 and serial DNP
3.0.
The third port is located in a removable
communications card. This plug-and-
play card can be easily changed in the
future as new standards arrive to the
market, thus providing a migration path
to the customer.
The protocol available for the third port
is DNP 3.0 over TCP/IP, UDP/IP, ModBus
Graphic 16 x 40 or text 4 x 20 LCD display
Fluorescent backlight to improve visibility
Multicolor programmable LEDs with label panel
/RFDO5HPRWH2 SXVKEXWWRQ ZLWK /('V
Key control for easy navigation
Ergonomic programmable keys
Electrically isolated front USB communication port
BROKEN
32
32N
51PH/V
51PL/V
67P
50N
51N
CONDUCTOR
R
R
3
3
3
3
3
3
3
3
METERING
81R
3
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
ANSI Device Numbers & Functions
Device
Function
Number
25
Synchrocheck
27/27X
Bus/Line Undervoltage
32
Sensitive Directional Power
32FP
Forward Power
32N
Wattmetric zero-sequence directional
46
Negative Sequence Time Overcurrent
47
Negative Sequence Voltage
48
Blocked Rotor
49
Thermal Image - overload protection
1
50 BF
Breaker Failure
50PH/PL
Phase Instantaneous Overcurrent (High/Low)
50N
Neutral Instantaneous Overcurrent
27X
50G
Ground Instantaneous Overcurrent
3
50SG
Sensitive Ground Instantaneous Overcurrent
59X
50IG
Isolated Ground Instantaneous Overcurrent
3
67N
51N
Neutral Time Overcurrent
3
25
51G
Ground Time Overcurrent
1
51SG
Sensitive Ground Time Overcurrent
51PH/V
Voltage Restraint Phase Time Overcurrent
51PL/V
59/59X
Bus/Line Overvoltage
59NH/NL
Neutral Overvoltage - High/Low
67P
Phase Directional Overcurrent
3V_0
67N
Neutral Directional Overcurrent
67G
Ground Directional Overcurrent
67SG
Sensitive Ground Directional Overcurrent
79
Autorecloser
81 U/O
Under/Over Frequency Broken Conductor
59NH
3
Detection
N/A
Load Encroachment
59NL
3
81R
Frequency Rate of Change
VTFF
VT Fuse Failure Detection
EN F650 BLOCK F.CDR
7&3,3 DQG ,(&