4.8 Residual current devices
Parameterization of the residual current device
Button for setting the tripping characteristic
This rotary switch can be used to change the tripping characteristic of the RCD520B
between type B (according to IEC 62423 and IEC 60947-2) and type B+ (according to
DIN VDE 0664-400 for I
The same conditions apply for type B+ as for type B, i.e. the tripping characteristics of type B
and type B+ are identical up to 1 kHz. With device type B+ however, the frequency range for
the detection of residual currents extends up to 20 kHz. Tripping takes place below 420 mA
within this frequency range to provide increased fire protection. With type B, the tripping
threshold increases above 1 kHz to prevent spurious tripping due to discharge currents,
particularly in conjunction with frequency converters.
434
Button for setting tripping characteristic type B / type B+
Setting button for response current I
Setting button for delay time Δt
= 30 to 300 mA and for frequencies over 1 kHz).
Δn
Δn
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03