Applications
3.2 Line protection applications of 3VA molded case circuit breakers
Neutral conductor protection N:
The neutral conductor protection function is available only for 3-pole molded case circuit
breakers with external current transformer for N conductor for 4-pole molded case circuit
breakers.
•
138
I
Adjustable in steps of 1 A
N
3-pole breakers with external current transformer for N conductor:
I
< 63 A: 0.4 to 1.6 x I
n
I
≥ 63 A: 0.2 to 1.6 I
n
4-pole breakers:
I
< 63 A: 0.4 to 1.6 x I
n
I
≥ 63 A: 0.2 to 1.0 or 1.6 x I
n
n
n
n
n
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03