Variants; Thermal-Magnetic Trip Units - Siemens SENTRON 3VA1 Manual

3va molded case circuit breakers with iec certificate
Table of Contents

Advertisement

3.2.1

Variants

3.2.1.1

Thermal-magnetic trip units

Derating
Thermal-magnetic trip units employ a temperature-dependent bimetal to provide overload
protection. The setting values are calibrated at an ambient temperature of +50 °C.
Compensation factors must be applied for ambient temperatures other than +50 °C.
You will find more information and derating factors in chapter Derating and temperature
compensation (Page 628).
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
3.2 Line protection applications of 3VA molded case circuit breakers
Applications