Variants - Siemens SENTRON 3VA1 Manual

3va molded case circuit breakers with iec certificate
Table of Contents

Advertisement

3.5.1

Variants

The same thermal-magnetic trip units used as line protection devices in AC installations are
also available for protecting DC installations.
However, a correction factor must be applied to the magnetic trip unit.
Example:
3VA1 160 A, TM240 ATAM:
If the switching device is to trip instantaneously in response to an overcurrent of 1200 A, the
parameter I
I
= 1200 A x 0.7 = 840 A.
i
For further information on trip units and details about setting parameters, please refer to
chapter "Line protection applications of 3VA molded case circuit breakers (Page 110)".
It is not possible to use electronic trip units for this application.
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
3.5 DC network applications of 3VA molded case circuit breakers
for instantaneous short-circuit protection (I) must be set to:
i
Applications
173