Note: When set to rising edge counting mode, trigger once, the value of DI is 00, when set to
falling edge counting mode, trigger once, the value of DI is 01. Also 0xff means no change.
Frame
DI1
header
0xAA 0xBB
0x00
4.3.3. Digital output DO time setting
The setting of digital pulse output time is to set the digital output time, the corresponding Modbus
register is 40083 (0x0052), and its value range is 100-65535ms. If the value is less than 100ms, the
default digital output is closed to hold status, that is, the digital value remains on after the output is
closed. If it is set to 100ms and above, such as 500ms, after the digital output close command is sent,
the switch value close will be maintained for 500ms, and then automatically open 500ms later.
4.3.4. Switch value DO restart output status setting
Whether the device is powered off and restarted to maintain the status before power off or restart
to maintain a specific output status setting. This function is only valid when the device digital output
time setting register value is less than 100ms.
The corresponding Modbus register of the switch value restart output status setting is 40085
(0x0054), and its value range is 0x00-0x100. When the value of this register is 0x100, the last digital
output status is maintained after power-off and restart. When the value of this register is 0x00-0xFF,
the lower 8 bits determine the status of the digital output of the device restart, bit6 corresponds to DO6,
bit5 corresponds to DO5, bit4 corresponds to DO4, bit1 corresponds to DO1. For example, when power
is on, DO4 and DO2 are in closed status, DO3 and DO1 and other ports are in open status. The
corresponding register value is 0000 1010, that is, 0xa0, "1" is the closed state, and "0" is open status.

Important statement

Ebyte reserves the right of final interpretation and modification of all contents in this manual.
As the hardware and software of the product are continuously improved, this manual may be
changed without further notice. The latest version of the manual shall prevail.
It's everyone's responsibility to protect the environment: In order to reduce the use of paper, this
manual is printed in Chinese only,and the English manual only available in electronic documents.
If necessary, please download it from our official website. In addition, if users does not
specifically request it, when users order in bulk, we only provide product specifications according
DI2
DI3
DI4
0x00
0x01
0xff
DI5
DI6
0x00
0x00
DI7
DI8
0x00
0x00
0x05 0x97