7 Operation
7.1 Starting from a non-powered status
Application manual - FlexLoader Standard Safety Center
3HAC051769-001 Revision: E
1 Turn on the main power supply. Wait until all devices have started up.
2 Perform a power on safety check:
•
Press and restore at least one internal FlexLoader Standard Safety
Center emergency stop button.
•
Reset the emergency stop.
•
Open and close at least one internal FlexLoader Standard Safety Center
cell door.
•
Reset the door status by shortly turning the reset key.
Optionally, if a light curtain is present, a long light curtain reset may
be needed (0.5 s) first, followed by a second reset for the whole cell.
3 Check the function of the external emergency stop
4 Check the function of the external protective stop (if present).
DANGER
Do not continue to work until the safety circuits are functioning correctly.
© Copyright 2014-2020 ABB. All rights reserved.
7.1 Starting from a non-powered status
7 Operation
45