PTAC Installation Recommendations

PTAC Installation Recommendations
For proper PTAC unit performance and maximum operating life refer to the minimum installation clear-
ances below:
Figure 1
PTAC units should be installed
no closer than 12" apart when
two units are side by side. If
three or more PTAC units are to
operate next to one another allow
a minimum of 36" between units.
Also, a vertical clearance of 60"
should be maintained between
units installed. In the interior
of the room the unit should be
located a minimum of 1/4" from
the floor and a minimum of 36"
from the ceiling.
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
Figure 2
For minor obstructions
such as lamp poles or small
shrubbery a clearance of
12" from the outdoor louver
should be maintained.
For major obstructions such
as a solid fence, wall or
other heat rejecting device
like a condensing unit, a
minimum distance of 36"
should be kept.
The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other
installation arrangements. By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.
28

INSTALLATION

60" VERTICAL
MIMUMUM
BETWEEN
PTACs
P
T
A
C
12" MINIMUM, MINOR
OBSTRUCTIONS
36" MIMUMUM, MAJOR
OBSTRUCTIONS
CONDENSING UNIT
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
TYPICAL
WINDOW
36"
60"
12"
VIEW: OUTSIDE BUILDING ELEVATION
TYPICAL BUILDING ( PLAN VIEW )
36"
PTAC
12"
36"
POLE
FENCE OR WALL
TWO ADJACENT PTACs
12" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
6"
36"
P
T
A
C
SHRUB
FRP001
FRP002
5