D+H RZN 4416-M Instructions For Use Manual page 18

Smoke vent system
Hide thumbs Also See for RZN 4416-M:
Table of Contents

Advertisement

Codification of Line S1, S3
Switch 1 on ON =
Switch
2 on ON
=
Dip switch 2 must be switched on OFF, when remote reset is desired of smoke detectors by the
smoke vent button.
Switch
3 on ON
= Line fault = alarm
Switch
4
=
Codification of Control Panel S6
Switch 1 on ON
Switch 1 on OFF =
Switch 2 on ON
Switch 3 on ON
Switch 4 on ON
Switch 5
Switch 6 on ON
Switch 7
Switch 8
18/20
RZN 4416-M Rev.:1.1
Two-smoke detectors dependency
Alarm will be triggered only, if at least two smoke detectors of one line respond.
False alarm of one smoke detector will be prevented.
See also page 14 about this.
Attention!
Two smoke detectors in one room must be always installed.
If only one smoke detector is connected to one line, switch is on OFF!
Smoke detector alarm can be reset only in control panel
Smoke detector alarm can
vent button.
The control panel will be switched on alarm, that means the
a
line fault
(e.g. at an interrupted detector line or short circuit).
idle
= Line 2 on group 3
Line 2 is also effective on group 3
Group 3 is independent of line 2
= Central alarm
In case of alarm of one line, the other line will be set on alarm as well
= Power failure-CLOSED
If the power supply breaks down, the drive will close.
Only when group-DIP switch 4 (key operation in CLOSED-direction) =
Bus control
=
Factory-setting must be on
=
idle
= LED Test / Reset WDT error (Watch Dog Timer)
Actuate DIP-switch (ON / OFF).
LED's will light up for 3 seconds in control panel
=
idle
=
idle
(Only in conjunction with FO 1362)
not
be reset by single pressing on button in smoke
"OFF"
smoke vent opens
at
ON