Informations for Starting
Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel.
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
10kΩ resistance in
smoke vent button?
10kΩ resistance in
Stop module 2x47kΩ
mains control
accumulator lines control
Performance check alarm/reset and ventilation
vent flap opens and
16/20
RZN 4416-M Rev.:1.1
All cable
no
connected?
yes
yes
Factory-set?
no
(Dip switch)
yes
no
yes
no
fire detector?
yes
no
in conduit box?
yes
Connect mains
no
lightens?
yes
Connect
no
lightens?
yes
Smoke
no
closes?
Partial or incomplete connection of components can
cause malfunction.
Check following connections: mains 230V, drives,
smoke vent buttons, when necessary fire detectors
and vent buttons. See wiring and connection plans
page 9-15.
Delivery condition of DIP-switches
see page 17.
Resistance must be cramped in electric last button on
binding posts 3/ 8 (RT 43-H) or binding posts 3/ 7
(RT 42). See connection plan page 9-15.
Resistance must be cramped in last or only fire detector
on binding post 2 and 4 (type FO/FT). Resistance
remains in control panel between binding post RM 1
and 2, when no fire detector available.
See connection plan page 9-15.
Cramp stop module on last or only drive in conduit box
on wire 5 yellow, 6 black, 7 black. See connection plan
page 9-15.
Check line safety fuse in E distribution and fuse mains
in control panel.
Mains still not available or line switch
on "0" or one of fuses faulty.
Possibly change poles in drive.