INSTALLATION MAGIC
MAGIC 105°

PRE-INSTALLATION CHECKS

The leaf must be fixed firmily on the hinges to the pillars, must not be flexible during the
movement and must move without frictions.
Before the installation of MAGIC, verify all dimensions etc.
There's no need for any modification, if the gate is like that shown in Fig. 1.
Gate features must be uniformed with the standards and laws in force. The gate
can be automated only if it is in a good condition and its conditions comply with the EN
12604 norm.
- The gate leaf does not have to have a pedestrian opening. In the opposite case it is
necessary to take the appropriate steps, in accordance with EN 12453 norm (for instance;
by preventing the operation of the motor when the pedestrian opening is opened, by
installing a safety microswitch connected with the control panel).
- No mechanical stop shall be on top of the gate, since mechanical stops are not safe
enough.
PREPARE THE CEMENTATION OF THE BOX
- Dig the pit fully up to the wall or gate post, keeping to the dimensions indicated in the
drawing and remembering that the hinge centre should fall half way along the Ø 500
dimension (fig. 5).
- Attach a 50 mm PVC tube to the water drain outlet on one side of the box, and a
heavy duty flexible insulating tube of Ø 32 mm max to the power cable outlet (Electrical
connections are made remote from the unit internally of a sealed junction box, which
can be either let into a wall or surface mounted, but must in any event be installed at a
minimum height above ground sufficient to ensure compliance with safety standards).
- Position the foundation box in the pit so that the topmost surface of the cover is flush with
the finished floor or paving.
MAGIC 105° INSTALLATION
- Anchor the box with cement mortar, taking care that none of the mix finds its way into the
enclosure, and checking that the shorter sides are faultlessly parallel with the gate
when in the SHUT position.
- Couple the transmission lever to the output shaft after you have greased it, checking first
that the bronze thrust bearing is fitted to the shaft.
The connection between gate and lever can be made as indicated in figs 7 and 8.
NB - When converting an existing gate with a load bearing support at ground level, the
MAGIC unit can be utilized as a replacement support (see installation fig. 8).
- Insert the bolts for cover fixing in places cut into the foundation box.
MAGIC 180°
3
Parts to install meeting the EN 12453 standard
COMMAND TYPE
with manned
operation
with visible impulses
(e.g. sensor)
with
not
visible
impulses
(e.g. remote control
device)
automatic
* a typical example are those shutters which do not have access to any public way
A: Command button with manned operation (that is, operating as long as activated),
like code ACG2013
B: Key selector with manned operation, like code ACG1010
C: Adjustable power of the motor
D: Safety strips and/or other safety devices to keep thrust force within the limits of
EN12453 regulation - Appendix A.
E: Photocells, like code ACG8026 (To apply every 60÷70cm for all the height of the
column of the gate up to a maximum of 2,5m - EN 12445 point 7.3.2.1)
A
22
USE OF THE SHUTTER
Skilled persons
Skilled persons
(out of public
(public area)
area*)
A
B
C or E
C or E
C or E
C and D, or E
C and D, or E
C and D, or E
B
4
Unrestricted use
non possibile
C and D, or E
C and D, or E
C and D, or E
5
6