As such, the electric signal is reduced to stop the oscillation of the piezo sensor. The electric signal is detected by the electronic circuit to operate the relay, so that the state can be detected with the contact output. HOUSING CABLE ENTRY CONNECTION FLANGE CONNECTION TUNING FORK EXTENSION PIPE SCREW HITROL CO., LTD.
SCS 14 SUS 316L+SCS 14 Process Connection PT 1-1/2”(M) PT 1-1/2”(M) (Std.), 2” Flange Housing ; Cable Entry AL. ; 2-PF 3/4”(F) (Std.) Installation Side Side or Top Contact Rating AC 250V, 5A / DC 30V, 5A HITROL CO., LTD.
Sensor shall be installed at the place far from inlet of the tank and protector shall be ■ installed in order to protect the sensor from damage by falling medium if it is installed at the inlet. (Refer to Fig. 1) HITROL CO., LTD.
Sensor shall be installed at the place far from inlet of the tank. ■ Sun cover shall be installed to protect the housing from the damage by direct ■ sunlight. (Refer to Fig. 1.) Sun Cover Protector Ⅹ Ⅹ <Fig. 1.> HITROL CO., LTD.
500N HTM-20N-C Max. Process Pressure Up to 10kg/㎠(150#) HTM(HPV)-20N-A / HTM(HPV)-20N-B 최대 Up to 2kg/㎠ HTM-20N-C Good for 0~100% Relative Humidity (Ratio between the vapors in the air and that required for saturation at the same temperature) HITROL CO., LTD.
- It doesn’t matter if the order of STEP 1 and STEP2 is changed. - When STEP 3 setup, all relay settings are initialized. (Delay Time: 1 Sec., Return Time: 1 Sec., Relay Out: Normal Closed) HITROL CO., LTD.
- It doesn’t matter if the order of STEP 1 and STEP2 is changed. - When STEP 3 setup, all relay settings are initialized. (Delay Time: 1 Sec., Return Time: 1 Sec., Relay Out: Normal Closed) HITROL CO., LTD.
Changes the relay contact time Enters the relay delay and return setting mode Enters the sensitivity Threshold is reached with the relay delay time Turned on and off YELLOW setting. Blinking No factory max. and min. value settings HITROL CO., LTD.
It there is explosive gas in the atmosphere, do not open the cover. ■ Remove it with the power disconnected. ■ Make sure that any o-ring or gasket is not damaged while opening or closing the cover. ■ HITROL CO., LTD.
Page 13
(Ex-proof) Make sure to insert a washer if the terminal lug is removed from ground terminal and then re- connected. (Loosening prevention) Internal Grounding (Wiring by the HITROL) External Grounding 4㎟ (4mmSQ) HEAD Internal Grounding / External Grounding HITROL CO., LTD.
Page 14
- The product identification mark is attached onto the housing and shows the model name, serial number, working temperature, working pressure, and matters regarding output. The serial number is a unique manufacturing number for the identification of products. Weather-proof Version Ex-proof Version HITROL CO., LTD.
Page 15
You can request A/S at our website or by contacting our headquarters. ■ Headquarters ․ Factory ․ Laboratory Contact Number ADDRESS: HITROL CO., LTD 141, Palhakgol-gil, Jori-eup, Paju-si, Gyeonggi-do, Korea T E L : 031-950-9700 (Headquarters & A/S) F A X : 031-943-5600 (Headquarters & A/S)