7 Disturbances, Maintenance, Cleaning

This chapter describes possible causes for disturbances and measures for their removal. In case of increased disturbances, please follow the
measures for fault clearance in chapter  7.1.
In case of disturbances that cannot be eliminated by following the advice and the fault clearance measures given here, please contact the
manufacturer (see second page).

7.1 Fault Clearance

CAUTION!
The device, the connection line and the signal cable must not be installed next to sources of interference that emit
strong inductive or capacitive interference or strong electrostatic fields.
External perturbations can be avoided thorough suitable cable routing.
The screen of the signal output cable should only be connected to the following circuit on one side. The screens
should not be grounded on both sides. Signal cables always have to be routed separately from the load power line.
A safety distance of at least 0,5 m has to be kept from inductive and capacitive sources of interference such as con-
tactors, relays, motors, switching power supplies, clocked controllers etc!
If interferences occur in spite of all the items stated above being observed, please proceed as follows:
1.
2.
3.
4.
5.

7.2 Re-start after Fault Clearance

After the fault clearance:
1.
Reset the emergency stop mechanism if necessary
2.
Reset the error report at the super-ordinate system if necessary.
3.
Ensure that there are no persons in the danger area.
4.
Follow the instructions from chapter  5.
WARNING!
Danger of injury through non-conventional fault clearance!
Non-conventional fault clearance can lead to severe injuries and damage of property.
Therefore:
If components need to be replaced:
Installation of RC-circuits via contactor coils of AC-contactors (e.g. 0,1 µF / 100 Ω)
Installation of recovery diodes via DC-inductors
Installation of RC-circuits via the different motor phases (in the terminal box of the motor)
Do not connect protective earth and ground
Connect a mains filter ahead of the external power pack
Any work to clear the faults may only be performed by sufficiently qualified staff
Arrange enough space before starting the works
Make sure that the mounting area is clean and tidy. Loose components and tools are sources of accidents.
Pay attention to a correct installation of the spare parts.
Reinstall all the fixing elements properly
Before turning on the device, ensure that all covers and safety equipment is installed correctly and functions
properly
Disturbances, Maintenance, Cleaning
- 18 -