(2) Parts list
Part
Name
number
1)
Connector
connector
2)
cover
paired sealed
3)
cable
4)
FG cable
(3) Assembly
1) 2)
POINT
· The grounding wire (green wire,approx.1m) coming out of the connector of the
user-fabricated connection cable must be connected to the control box or the
like.
· Grounding should be independent where possible.
· Use class 3 grounding method (grounding resistance is 100•max.).
· The grounding point should be as near as possible to the external I/O module to
minimize the grounding cable length.
· Adjust the grounding cable length according to the grounding position and install
a terminal or the like for grounding.
· When grounding, always connect the FG cable for connection with the GOT's
power supply terminal block and the FG wire of the user-fabricated connection
cable separately.
FCN-361J040-AU
FCN-360C040-B
UL 2464 AWG
UL 1015 AWG14 or equivalent
4)
3)
17