Page 1
Enclosure cooling unit SK 3185.330 Assembly and operating instructions...
Page 2
Rittal GmbH & Co. KG Auf dem Stützelberg 35745 Herborn Germany Phone: +49(0)2772 505-0 Fax: +49(0)2772 505-2319 E-mail: info@rittal.com www.rittal.com www.rittal.de We are always happy to answer any technical questions regarding our entire range of products. Rittal enclosure cooling unit Blue e+ Outdoor...
7.2.2 Changing a parameter value ....... 24 Information menu ........24 7.3.1 Temperature information ........24 7.3.2 Device information ..........24 7.3.3 Efficiency information .......... 25 Configuration menu........25 7.4.1 Temperature ............25 7.4.2 Network ............. 27 Rittal enclosure cooling unit Blue e+ Outdoor...
1 Notes on documentation Notes on documentation CE labelling Rittal GmbH & Co. KG confirms the conformity of the cooling unit with the European Union's Machinery Direc- tive 2006/42/EC and EMC Directive 2014/30/EC. A corresponding declaration of conformity has been is- sued and enclosed with the unit.
It is therefore particularly important to brace the unit – Use only original Rittal products or products recom- and prevent it from becoming unbalanced once the mended by Rittal in conjunction with the cooling unit.
R134a is circulating. This refrigerant is very environmentally friend- ly, thanks to the following properties: – Chlorine-free – Does not deplete the ozone layer (ozone destruction potential ODP = 0) Rittal enclosure cooling unit Blue e+ Outdoor...
Control downwards out of the unit via a drain pipe on the evap- Rittal enclosure cooling units are fitted with a controller orator coil divider panel. For this purpose, a hose may be for setting the functions of the cooling unit.
Rittal GmbH & Co. KG is not liable for any damage which may result from failure to comply with the documenta- tion provided. The same applies to failure to comply with the valid documentation for any accessories used.
Page 9
3 Product description Qty. Description – Mounting frame – Signal connector X2 – Connector X1 – T-rail – Ferrite core Tab. 1: Scope of supply Rittal enclosure cooling unit Blue e+ Outdoor...
Protect the lifting gear on the crane hook from load de- livery, should be reported immediately, in flection, because the load's centre of gravity may be writing, to the shipping company and to Rittal off-centre. GmbH & Co. KG. ...
All work must be carried out in ac- cordance with electrical engineering Size of installation room regulations. – Unit SK 3185.330 must not be installed in rooms of less than 3 m³. The cooling unit may only be connected after the aforementioned personnel have...
Note: When mounting unit SK 3185.330, the mini- mum dimensions of the enclosure are 600 mm x 1200 mm (width x height), both on the door and on the side panel.
5.3.3 Make a mounting cut-out in the enclosure Twin-walled enclosure For mounting on a twin-walled enclosure, the appropri- ate door or side panel must be purchased from Rittal. Please contact us to discuss your requirements. Single-walled enclosure For mounting on a single-walled enclosure, a suitable mounting cut-out must be made.
Fig. 9: Laying the seal Screw the two threaded bolts into the blind threaded bushes at the bottom rear of the cooling unit. Rittal enclosure cooling unit Blue e+ Outdoor...
Page 15
L-shaped brackets. washers and hex nuts (maximum torque: 5 Nm). Once again, pay particular attention to the correct orienta- tion of the corner brackets. Rittal enclosure cooling unit Blue e+ Outdoor...
– When mounting on a single-walled enclosure with mounting frame, screws with an under-head gasket or blind rivet nuts may be used. Please contact Rittal Remove the mounting frame from the packaging and if you require further information.
Ensure that the seal has been pressed into the mount- out of the cooling unit pressurelessly. A suitable hose is ing frame around the entire circumference. available as an accessory from Rittal (see section 13 Lift up the cooling unit, preferably from a crane bracket "Accessories").
– To ensure the proper functioning of internal presso- half-way up. stats in the event of a malfunction, a slow (time delay) Rittal enclosure cooling unit Blue e+ Outdoor...
Page 19
– Outgoing equipment is monitored by the inverter, and deactivated in the event of a malfunction in the elec- tricity supply. Door limit switch – Each door limit switch can only be assigned to one cooling unit. Rittal enclosure cooling unit Blue e+ Outdoor...
T-rail (fig. 31). Remove the mains connector from the dispatch bag and connect to the mains as shown on the connection diagram (fig. 29 or fig. 30). Fig. 31: Attach the T-rail (example illustration) Rittal enclosure cooling unit Blue e+ Outdoor...
A tablet or laptop may be connected here for easy configuration of the unit. Connect a tablet or laptop with installed RiDiag III soft- ware to the micro-USB interface. Rittal enclosure cooling unit Blue e+ Outdoor...
Next, switch on the voltage supply to the cooling unit. The Rittal logo will initially appear on the display, fol- lowed a short time later by the start screen. You can now make your individual settings on the unit, e.g.
Self-test (if initiated) sages, as well as the option of contacting the Rittal Ser- vice team directly. NFC connection (max. Note: 120 seconds after con- ...
This title can be assigned using the Efficiency info RiDiag software or the Blue e+ app to distin- guish between individual units. Act. control mode Tab. 6: "Information" zone Tab. 8: "Device information" zone Rittal enclosure cooling unit Blue e+ Outdoor...
– be influenced directly by the cold air expelled from the Filter mats (no function) cooling unit, – be influenced by external heat sources or heat radia- tion, Tab. 10: "Configuration" zone – be exposed to humidity, Rittal enclosure cooling unit Blue e+ Outdoor...
Page 26
The corresponding symbol for the chosen control mode is likewise displayed on the overview page. Note: The external temperature sensor is available as accessory from Rittal (see section 13 "Ac- cessories"). Change the setpoint using the "Up" and "Down" ar- rows or select the required temperature directly.
Page through the list using the "Up" and "Down" ar- display. rows. Confirm your entry with "OK". Click on the desired entries to display the IPv6 ad- dresses. Parameter Setting DHCP off/on Tab. 18: IPv6 settings Rittal enclosure cooling unit Blue e+ Outdoor...
Switch the alarm relay as a normally closed function applies. contact. Tab. 20: Switch logic of the alarm relay System messages We distinguish between three different types of system messages on the unit: Rittal enclosure cooling unit Blue e+ Outdoor...
The individual messages are arranged in ascending or- der as they occur according to the above three catego- Fig. 37: Screen showing error messages ries. If an error message can only be resolved by the Rittal "Errors" menu Service team, the "Service" symbol will additionally Error message appear after the error message.
If no blockage is visible, please replace the fan in the internal circuit. The required spare part may be or- dered directly from Rittal using the Blue e+ app. Please use the contact form "Generate service order".
Page 31
The fan in the internal circuit of your cooling unit is defective. Please re- place the fan in the internal circuit. The required spare part may be or- dered directly from Rittal using the Blue e+ app. Please use the contact form "Generate malfunction report".
Page 32
Rittal Service team directly. Alarm act.cooling – The active cooling function of your unit is defective. Please contact the Rittal Service team immediately, and/or check the rating of your cooling unit. Tab. 22: Error messages Rittal enclosure cooling unit Blue e+ Outdoor...
Secure the power supply to prevent it being switched ted with a temperature monitor. back on accidentally. Rittal recommends that the cooling unit fans should be Disconnect the electrical connection cable of the cool- checked e.g. for unusual running noises after around ing unit from the power supply at the connection box.
Re-fit the cover onto the enclosure in the reverse or- der. Please note, it is important to ensure that the PE con- ductor connecting the cover to the enclosure is con- nected at both ends. Rittal enclosure cooling unit Blue e+ Outdoor...
Facilities for disposal are available at the Rittal plant or a specialist company. Give us a call (see section 14 "Customer service addresses"). Rittal enclosure cooling unit Blue e+ Outdoor...
15 A (SCCR = 14 kA) SCCR [kA] EN 61439 Cable cross-section [mm²] UL 508A ≥2.1 oder ≤14 AWG) Overvoltage category Level of contamination Protection category IP 4ating Tab. 23: Technical specifications Blue e+ Outdoor Rittal enclosure cooling unit Blue e+ Outdoor...
Page 37
[g] 1430 e [t] 1.07 Other Weight [kg] Storage temperature range [°C] -40…+70 Noise pressure level Lp [dB(A)] <68 Approvals UL File number: SA8250 E491171 Tab. 23: Technical specifications Blue e+ Outdoor Rittal enclosure cooling unit Blue e+ Outdoor...
11 List of spare parts List of spare parts Spare parts may be ordered directly from the Rittal web- Note: site. The components used are Rittal-specific – https://www.rittal.com/com-en/Services/Ersatzteile components. We recommend using only Enter the model number of your device.
12.1 Representation of mounting cut-outs 12.1.1 Mounting on single-walled enclosure 12.1.2 Mounting on single-walled enclosure panels without a mounting frame panels with a mounting frame 112,5 112,5 Fig. 43: Mounting cut-out Fig. 44: Mounting cut-out Rittal enclosure cooling unit Blue e+ Outdoor...
14 "Customer service address- es". Item Model No. Door limit switch SK 4127.010 Condensate water hose SK 3301.612 External temperature sensor SK 3124.400 IoT Interface SK 3124.300 RiDiag III SK 3159.300 Tab. 24: List of accessories Rittal enclosure cooling unit Blue e+ Outdoor...
– http://www.rittal.com – http://www.rittal.com – Enquire at the relevant national company – http://www.rittal.com/de_de/service_contact/index.asp Other service contacts worldwide: Rittal International Service HUBs (see section 14 "Customer service address- es") Tab. 26: Service contacts worldwide Rittal enclosure cooling unit Blue e+ Outdoor...
Page 47
Notes Rittal enclosure cooling unit Blue e+ Outdoor...
Page 48
◾ Climate Control ◾ IT Infrastructure ◾ Software & Services You can find the contact details of all Rittal companies throughout the world here. www.rittal.com/contact RITTAL GmbH & Co. KG Auf dem Stuetzelberg · 35745 Herborn · Germany Phone +49 2772 505-0...
Need help?
Do you have a question about the SK 3185.330 and is the answer not in the manual?
Questions and answers