Mounting Instructions - S&P REB-5 Manual

Single-phase speed controller
Hide thumbs Also See for REB-5:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 4
SINGLE-PHASE SPEED
CONTROLLER
TECHNICAL DATA
- Voltage 230V 50Hz
- Max. current 5A (REB-5) – 10A (REB-
10)
- Minimum load 0,8A (REB-5) – 1A
(REB-10)
- Control by potentiometer
- Regulation from max to min
- Switch with indicator lamp
- Connection by terminals
- Minimum speed adjustable
- Maximum speed adjustable
- Enclosure IP54
- EMC filter according to EN55014
standard
- Fuse protection HF 5A (REB-5) – 10A
(REB-10)
- Switch for kick start selection (SW1-1)
- Start with selectable acceleration ramp
(SW1-2)
- Dimensions (mm) 164x96x85 (REB-5)
– 205x127x95 (REB-10)
1.
Hold cover screw
2.
Button
3.
Input wires
4.
Clamping holes
5.
Connection terminal
6.
Switch with indicator lamp
7.
Fuse
8.
Minimum speed adjustment
9.
Maximum speed adjustment
10. Connector potentiometer
11. Switch for kick start selection
12. Switch
for
selection

MOUNTING INSTRUCTIONS

The under detailed rules must be strictly
followed for the correct use of the
equipment:
1. Take off the box cover loosening the
screws (it is not necessary to take off
the
button).
potentiometer is connected, by means
of three wires, to the base of the
regulator.
acceleration
ramp
Attention:
the
2. Put the switch in OFF position.
3. Connect the earth, the fans and 230V
line to terminal according to the
included scheme.
4. Put the switch in the ON position and
adjust the minimum speed by means
of and maximum speed by means of.
IMPORTANT: In case of regulating
motors it´s necessary to have a
minimum speed of 80V.
5. Close the box, and verify that it works
fine with the potentiometer.
NOTE
SW1-1: This regulator incorporates, if
selected, the new system protection with
kick start:
When the regulator is connected, the
motor works at 100% during about 10
seconds, this function is repeat each
stop and when connected the regulator.
SW1-2: This regulator, if selected, has
an acceleration ramp (approx. 10s (REB-
5) – 30s (REB-10) from 0 to 100%).
ATTENTION
- The operating position must be as
shown below.
- It´s essential to connect the earth line
to the regulator.
- S&P does not assume the damages
due
a
faulty
regulator.
The main line of regulator and the output
to the fans must have the suitable
section by the maximum current of the
regulator and the installation mainly has
to
comply
with
standards.
(S&P reserves the right to make changes without notice).