TERMINAL IDENTIFICATION AND FUNCTION
Damper
Supported output types:
• 0-10 Vdc Direct Acting
• 0-10 Vdc Reverse Acting
• 2-10 Vdc Direct Acting
• 2-10 Vdc Reverse Acting
• Floating
Recommended Damper Actuator Type: Elec, Prop, 0-10 Vdc, NSR, 24 Vac, Plenum, 35 in-lb or equivalent.
Table 3: Terminal Identification for Damper Actuator.
0-10 Vdc Analog Actuator
Terminal
5
6, 18, or 21
11
Floating Actuator*
Terminal
6, 18, or 21
9
11
*Floating actuation time limits:
• Minimum = 0.5 minutes.
• Maximum = 9.0 minutes.
• Increment = 0.5 minutes.
Changeover and Supply Sensors
The Room Controller is compatible with remote mount temperature sensors using 10K Type 2 NTC thermistors.
Table 4: Terminal Identification for Changeover and Supply Sensors.
Changeover and Supply Sensors
Terminal
19
6, 18, or 21
22
14
RC / 24 Vac ~ Hot
C / 24 Vac ~ Common
C / 24 Vac ~ Common
Name
UI19
C / 24 Vac ~ Common
UI22
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Name
UO11
Name
UO9
UO11
Connection
Changeover Sensor
24 Vac ~ Common
Supply Sensor
Connection
24 Vac ~ Hot
24 Vac ~ Common
0-10 Vdc Output
Connection
24 Vac ~ Common
Close Actuator
Open Actuator