7.3 Calibration of safety components

Any work on the unit must be carried out by qualified authorised personnel. Incorrect calibration values can
cause serious damage to the unit and harm people.
The control and safety equipment is calibrated and tested in the factory before the unit is shipped.
However, after the unit has been started, the safety devices must be checked (only the high and low pressure switches).
The checks must be carried out as described in the "Periodic checks" chapter.
Values for cooling and HPW versions only
Control and safety components
High-pressure switch
High pressure safety valve
Low pressure safety valve (only 143.2 and
159.2)
Values for OH versions
Control and safety components
High-pressure switch
High pressure safety valve
Low pressure safety valve (only 143.2 and
159.2)
58
Translation from original instructions
Activation set point
18 barg
20 barg
16 barg
Activation set point
22 barg
24,5 barg
16 barg
Differential
7,5 barg
-
-
Differential
7,5 barg
-
-
We reserve the right to make changes without any prior notice.
Reset
Manual
-
-
Reset
Manual
-
-