2.2.7

Condensation control at the source hydraulic circuit

The temperature and flow rate of the source circuit water must be maintained within the operating limits stated in the Tech-
nical Catalogue.
It is essential for the water to come in at the connection indicated in the dimensional diagram and with the
relevant plate on the unit.
A modulating three-way valve that will ensure an incoming water temperature within the operating limits
stated in the Technical Catalogue must be installed for correct operation of the unit.
02
Condenser
EL
Motor-driven pump
V3
Thermostatic three-way valve
The three-way modulating valve can be supplied as accessory by the manufacturer.
As accessory, the signal to control it can also be supplied with the modulating valve.
The hydraulic connection of the three-way modulating valve must be made as shown in the illustration.
02
Condenser
EL
Motor-driven pump
V3
Three-way valve
16
Translation from original instructions
Fig. 1 3-way valve installation layout
Fig. 2 Hydraulic connection of three-way valve