Making The Piping For The Lc Versions - Swegon BlueBox Omega Sky Installation, Use And Maintenance Manual

Table of Contents

Advertisement

6.8.2

Making the piping for the LC versions

Recommended diameters for the LC versions - The thickness of the pipe must be compatible with the refrigerant
used and with current regulations.
Model
Circuits
43.1
1
50.1
1
58.1
1
66.1
1
70.1
1
79.1
1
63.2
1 - 2
72.2
1 - 2
88.2
1 - 2
101.2
1 - 2
116.2
1 - 2
132.2
1 - 2
143.2
1 - 2
159.2
1 - 2
The above mentioned diameters were chosen in order to optimise the performance of the units, contempo-
raneously ensuring the proper operation at the permissible conditions and to contain the refrigerant charge
within reasonable limits.
48
Translation from original instructions
Equivalent length 10 m
Gas [mm]
Liquid [mm]
76
54
76
54
76
54
89
67
89
67
89
67
67
42
67
42
76
54
76
54
76
54
89
67
89
67
89
67
Equivalent length 20 m
Gas [mm]
Liquid [mm]
76
54
76
54
89
54
89
67
89
67
89
67
67
42
67
42
76
54
76
54
89
54
89
67
89
67
89
67
We reserve the right to make changes without any prior notice.
Equivalent length 30 m
Gas [mm]
Liquid [mm]
76
54
76
54
89
54
89
67
89
67
89
67
67
42
67
42
76
54
76
54
89
54
89
67
89
67
89
67