17.4 Standardized Interface - Extinguishing

With this application it is possible to realize standardized interface >extinguishing< in accordance to the
VdS-2540 requirements for Extinguishing control systems.
Fire Alarm Control Panel
Extinguishing
command
Fault extinguishing system
Extinguishing system
triggeredreleased
Fig. 34: Wiring of the interface
The Inputs and Outputs are used as follows:
Input >Extinguishing<
A free selectable automatic detector zone MG1-MG8 of the LMST 8010 must be programmed as >Standard-
zone-Extinguishing<. The chosen detector zone is only operable with this assigned function.
Output >Failure extinguishing system<
A free selectable relay no. 1-8 of the LMST 8010 must be programmed with the corresponding jumpers as >not
monitored< and configured in the customer data with the status function >Fault<. Connect required resistors
R1+R2 (refer to figure above).
Output >Extinguishing system triggered<
A free selectable relay no. 1-8 of the LMST 8010 must be programmed with the corresponding jumpers as >not
monitored< and configured in the customer data with the status function > Extinguishing system triggered<.
Connect required resistors R3+R4 (refer to figure above).
According to VdS Guideline 2540, the terminal strips in the FACP and in LMST 8010 must be
labelled according to their respective function.
FB 798352 / 11.07
Extinguishing Control Computer 8010 - Series 2
R1
R2
R3
R4
Extinguishing control
system 8010
Automatic detector zone
Relay output A
Relay output B