Specifications - Honeywell Esser 2 Series Operation And Installation Instruction

Extinguishing control computer
Table of Contents

Advertisement

Available languages

Available languages

Extinguishing Control Computer 8010 - Series 2
19

Specifications

Main voltage
Rated frequency
Rated current
Battery capacity
Battery charging voltage
Ambient conditions
Ambient temperature
Storage temperature
Protection class
Protection rating
Housing
Colour
Weight
Dimensions (W x H x D):
VdS approval
CE certificate
Alarm zone inputs 1 to 8
Technical zones
Relay contacts
Relays No. 1 to 8
Relays No. 9 to 11
Relays No. 12 and 13
110
:
230 V AC
:
50 Hz
:
0.7 A
:
2 x 12 V / 24 Ah
:
13.65 V DC @ 25 °C
:
class 3k5 in accordance to DIN EN 60721-3-3
:
-5 °C to +45 °C
:
-10 °C to +50 °C
:
I in accordance with DIN EN 60950-1
:
IP 30
:
Sheet steel with swivel-mounted front door
:
Light grey, similar RAL 7035 / blue, similar RAL 5003
:
approx. 18.3 kg (without rechargeable battery)
:
488 x 625 x 210 (mm)
:
G 200090
:
0786-CPD-20223
:
Monitored differential alarm zone for connecting automatic fire detectors.
End-of-line resistor (10kΩ normal / 1kΩ alarm)
:
Monitored differential alarm zone for connecting
Manual Call Points (MCP) series 9000 or dry contacts.
End-of-line resistor (10kΩ normal / 1kΩ alarm)
:
Changeover contacts, max. 30 V DC / 2 A
Operating mode potential-free or positive-switching / monitoring can be
set via plug-in jumpers
:
Changeover contacts, max. 30 V DC / 2 A
Programmable, relays 10 and 11 with selectable function for
>Emergency Operation Trouble< and >Emergency Operation Fire<
:
Dry contact (NO), max. 230 V AC / 2 A,
suitable for switching AC mains voltage