Safety Information
6
Parameter differences from defaults
Table 6-1
Macro 6501/6502: Fan/Pump Control - No Bypass (Eur, 50 Hz)
Parameter
0.01
Minimum reference clamp
0.03
Acceleration rate 1
0.04
Deceleration rate 1
0.20
T7 Analog input 2 destination
1.51
Power-up keyboard control mode reference
1.52
Enable hand/off/auto keypad operating mode
2.06
S ramp enable
2.07
S ramp acceleration limit
6.49
Enable Date/Time in trip log
7.10
T5/6 Analog input destination
Table 6-2 Macro 6601/6602: Fan/Pump Control - No Bypass (USA, 60 Hz)
Parameter
0.01
Minimum reference clamp
0.03
Acceleration rate 1
0.04
Deceleration rate 1
0.20
T7 Analog input 2 destination
1.51
Power-up keyboard control mode reference
1.52
Enable hand/off/auto keypad operating mode
2.06
S ramp enable
2.07
S ramp acceleration limit
6.49
Enable Date/Time in trip log
7.10
T5/6 Analog input destination
Table 6-3 Macro 6603/6604: Fan/Pump Control - With Bypass (USA, 60 Hz)
Parameter
0.01
Minimum reference clamp
0.03
Acceleration rate 1
0.04
Deceleration rate 1
0.20
T7 Analog input 2 destination
1.51
Power-up keyboard control mode reference
Enable hand/off/auto keypad operating
1.52
mode
2.06
S ramp enable
2.07
S ramp acceleration limit
6.12
Enable stop key
6.49
Enable Date/Time in trip log
7.10
T5/6 Analog input destination
9.04
Logic Function Source 1
9.06
Logic Function Source 2
9.10
Logic Function 1 destination
NOTE
The actual acceleration/deceleration times are for a 100 Hz speed
reference. For 50 Hz, these settings must be divided by 0.5 and for 60
Hz these settings must be divided by 0.6. For example, for a 10 second
acceleration relevant to a 6 0Hz frequency reference, the acceleration
time must be set as 10/0.6 = 16.6 seconds.
Affinity Macro Guide
Issue Number: 2
Macros
Macros 6501/6502
{1.07}
{2.11}
{2.21}
{7.14}
Reset (0), lasT (1), pRs1 (2)
{1.07}
{2.11}
{2.21}
{7.14}
Reset (0), lasT (1), pRs1 (2)
{1.07}
{2.11}
{2.21}
{7.14}
Reset (0), lasT (1), pRs1 (2)
Macros 6601/6602
Macro Default( )
Range( )
Fan
± 3000.0 Hz
12.0 Hz
0.0 to 300.0 s/100 Hz
100.0
0.0 to 300.0 s/100 Hz
100.0
Pr 0.00 to Pr 50.99
Pr 1.36
Last (1)
0 to 3
Auto (1)
OFF (0) or On (1)
On (1)
2
50.0
0.0 to 300.0 s
/100 Hz
OFF (0) or On (1)
On (1)
Pr 0.00 to Pr 50.99
Pr 0.00
Macro Default( )
Range( )
Fan
± 3000.0 Hz
15.0 Hz
0.0 to 300.0 s/100 Hz
100.0
0.0 to 300.0 s/100 Hz
100.0
Pr 0.00 to Pr 50.99
Pr 1.36
Last (1)
0 to 3
Auto (1)
OFF (0) or On (1)
On (1)
2
60.0
0.0 to 300.0 s
/100 Hz
OFF (0) or On (1)
On (1)
Pr 0.00 to Pr 50.99
Pr 0.00
Macro Default( )
Range( )
Fan
± 3000.0 Hz
15.0 Hz
0.0 to 300.0 s/100 Hz
100.0
0.0 to 300.0 s/100 Hz
100.0
Pr 0.00 to Pr 50.99
Pr 1.36
Last (1)
0 to 3
Disable (0)
OFF (0) or On (1)
On (1)
0.0 to 300.0 s/100 Hz
60.0
OFF (0) or On (1)
On (1)
OFF (0) or On (1)
On (1)
Pr 0.00 to Pr 50.99
Pr 0.00
Pr 0.00 to Pr 50.99
Pr 8.03
Pr 0.00 to Pr 50.99
Pr 8.06
Pr 0.00 to Pr 50.99
Pr 1.43
Parameter differences from
Macros 6603/6604
defaults
Parameter Default( )
Pump
OL
5.0 Hz
0.0
EUR>40.0
16.6
USA>33.3
EUR>40.0
16.6
USA>33.3
Pr 1.36
Pr 1.37
Last (1)
rESET (0)
Auto (1)
Off (2)
On (1)
Off (0)
16.6
3.1
On (1)
Off (0)
Pr 0.00
Pr 1.36
Parameter Default( )
Pump
OL
6.0 Hz
0.0
EUR>40.0
16.6
USA>33.3
EUR>40.0
16.6
USA>33.3
Pr 1.36
Pr 1.37
Last (1)
rESET (0)
Auto (1)
Off (2)
On (1)
Off (0)
16.6
3.1
On (1)
Off (0)
Pr 0.00
Pr 1.36
Parameter Default( )
Pump
OL
6.0 Hz
0.0
EUR>40.0
16.6
USA>33.3
EUR>40.0
16.6
USA>33.3
Pr 1.36
Pr 1.37
Last (1)
rESET (0)
Disable (0)
Off (2)
On (1)
Off (0)
16.6
3.1
On (1)
Off (0)
On (1)
Off (0)
Pr 0.00
Pr 1.36
Pr 8.03
Pr 0.00
Pr 8.06
Pr 0.00
Pr 1.43
Pr 0.00
RFC
EUR>13.333
USA>11.111
EUR>13.333
USA>11.111
1.5
RFC
EUR>13.333
USA>11.111
EUR>13.333
USA>11.111
1.5
RFC
EUR>13.333
USA>11.111
EUR>13.333
USA>11.111
1.5
13