Panel Installation - Pepperl+Fuchs VisuNet FLX RM-320P Series Manual

Table of Contents

Advertisement

VisuNet FLX Panel
Mechanical Installation
Warning!
Proper installation!
It is the installer's responsibility to select a suitable location with sufficient strength to hold the
equipment. It is the installer's responsibility to select the proper screws based on the installa-
tion conditions.
Warning!
Proper sealing!
To assure proper sealing, the minimum wall thickness of 1 mm must be kept and it is necessary
to use the horizontal and vertical brackets included in the kit for panel mounting. The maximum
wall thickness for VisuNet FLX 21.5" panels is 3 mm, for 19" and 15.6" panels 4 mm.
4.2

Panel Installation

Caution!
Heat damage!
If the device is exposed to radiation from sunlight or other light or heat sources, it may overheat
and be damaged.
Do not expose the device to direct sunlight or other sources of light or heat!
Warning!
The use of the device is only permitted under the environmental conditions (temperature,
humidity, vibration and shock) which are specified in the data sheet.
Failure to observe any one of these conditions will invalidate the warranty of the device. Pep-
perl+Fuchs cannot be held liable for any damage arising from improper use and handling.
Danger!
Damage caused by condensation!
If the temperature of the device is different to that of the room in which it is located, condensa-
tion can occur.
Switch on the device only if it has acclimated to the ambient temperature!
Danger!
Danger resulting from damaged seals.
Explosion protection is no longer ensured if a system with damaged seals is used. NEVER use
a system with damaged seals in a hazardous area. If the seal is damaged in any way, return the
system to Pepperl+Fuchs at once and replace it with a new one.
23