Manual

Advertisement

Table of Contents
loading

Summary of Contents for Pepperl+Fuchs VisuNet FLX RM-320P Series

  • Page 1 VisuNet FLX Panel RM-320P-* PC-320P-* DM-320P-* Manual...
  • Page 2 Phone: +49 621 776 - 0 E-mail: info@de.pepperl-fuchs.com North American Headquarters Pepperl+Fuchs Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 425-3555 E-mail: sales@us.pepperl-fuchs.com Asia Headquarters Pepperl+Fuchs Pte. Ltd. P+F Building 18 Ayer Rajah Crescent Singapore 139942 Phone: +65 6779-9091 E-mail: sales@sg.pepperl-fuchs.com https://www.pepperl-fuchs.com...
  • Page 3: Table Of Contents

    VisuNet FLX Panel Contents History of the Manual ....................4 Introduction........................ 5 Content of this Document ................5 Manufacturer ....................5 Target Group, Personnel ................5 Symbols Used ....................6 Tolerances for Linear Dimensions ............... 7 Product Description ....................8 Overview ......................
  • Page 4: History Of The Manual

    VisuNet FLX Panel History of the Manual History of the Manual The following editions of the manual have been released: Version Comments 04/2021 First edition...
  • Page 5: Introduction

    Certificates • Control drawings • Additional documents Manufacturer Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany Internet: www.pepperl-fuchs.com Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismount- ing lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, com- missioning, operation, maintenance, and dismounting of the product.
  • Page 6: Symbols Used

    VisuNet FLX Panel Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid prop- erty damage.
  • Page 7: Tolerances For Linear Dimensions

    VisuNet FLX Panel Introduction Tolerances for Linear Dimensions For all dimension drawings (e.g. dimension drawings, etc.) the European dimension standards are valid. All dimensions are in mm. Unless otherwise specified, the following general tolerances are valid. Nominal dimension ranges General tolerance according to Nominal dimension range DIN ISO 2768 medium up to 6 mm...
  • Page 8: Product Description

    Display and seals are chemically resistant to typical cleaning agents. In addition, individual solutions can also be created and manufactured at Pepperl+Fuchs' Solu- tion Engineering Centers (SEC), which are located around the world.
  • Page 9 RAM available as 4 GB, 8 GB ans 16 GB DDR4-2133 Storage available as 32 GB, 256 GB and 512 GB, expandable with quali- fied Pepperl+Fuchs components. Computing Unit: (TCU, PCU or DMU): processor, SSD and memory, Ex circuits, interface modules An extra system housing is available in which the VisuNet FLX panel can be easily installed in.
  • Page 10: Reference Documents

    VisuNet FLX Panel Product Description Reference Documents Important Instructions and Manuals for Operating the Device Documentation Contents You are here: • Panel installation VisuNet FLX • Information regarding 21.5", 19" and 15.6" DPU Panel manual • Connecting the BPC3200-* to the DPU3200-* •...
  • Page 11: Technical Data

    VisuNet FLX Panel Product Description Technical Data PC-320P-* (Personal Computer) General specifications Type Personal Computer Hardware Processor Intel® Core™ i5-7300U Intel® Celeron™ 3965U 2x SO-DIMM slots, supports up to 32 GB DDR4-2133 (one SO-DIMM slot) Configurable RAM options: Industrial temperature grade (temperature option A): A: 1x 4 GB DDR4-2133 [Celeron] B: 1x 8 GB DDR4-2133 C: 1x 16 GB DDR4-2133...
  • Page 12 Configurable storage options: A: 32-GB M.2 SATA 3, industrial temperature grade [temperature class A] K: 32-GB M.2 SATA 3, wide temperature grade Software Operating system Pepperl+Fuchs VisuNet RM Shell 5 (based on Microsoft® Windows® 10 IoT Enterprise 2019 LTSC (x64))
  • Page 13 1 x DisplayPort 1.2 (DP++) 1 x mini DisplayPort 1.2 (DP++ w/ mono locking screw) 1 x Audio Line-out 2 x USB Ex i ports prepared for Pepperl+Fuchs intrinsically safe keyboard 2 x USB 3.1 Gen1 (5 Gbps) ports 1 x USB 2.0 port...
  • Page 14 VisuNet FLX Panel Product Description Directive conformity Electromagnetic compatibility Directive DIN EN 55035:2018-04 2014/30/EU Explosion protection Directive EN IEC 60079-0:2018 2014/34/EU EN IEC 60079-7:2015/A1:2018 EN 60079-11:2012 EN 60079-31:2014 RoHS Directive EN IEC 63000:2018 2011/65/EU (RoHS) Ambient conditions Operating tem- Temperature classes: perature A: 0 …...
  • Page 15 VisuNet FLX Panel Product Description Data for application in connection with hazardous areas (pending) EU-type examination certificate Marking Certificate in preparation. II 3 G Ex ec [ic] IIC T4 Gc II 3 D Ex tc [ic] IIIC T85°C Dc International approvals (pending) UL approval Approved for Certificate in preparation.
  • Page 16 VisuNet FLX Panel Product Description Indicators/operating means Resolution 22GT, 22FC, 15FC: 1920 x 1080 pixels (Full HD) Aspect Ratio (16:9) 19SC: 1280 x 1024 pixels (SXGA) Aspect Ratio (5:4) Color depth 24 bit (16.7 M) color Contrast Typically 22GT: 1000:1 22FC: 5000:1 19SC: 1000:1 15FC: 800:1...
  • Page 17 VisuNet FLX Panel Product Description Ambient conditions Relative humidity max. relative humidity 93% at 40°C (non-condensing) according to EN60068-2-78 Climatic condi- Passive cooling, no rotating parts tions Altitude Operating altitude max. 2000 m Shock resistance 18 shocks 15 g, 11 ms all axis, IEC 60068-2-27 Vibration resis- 10 ...
  • Page 18 VisuNet FLX Panel Product Description International approvals (pending) IECEx marking Ex ec [ic] IIC T4 Gc Ex tc [ic] IIIC T85°C Dc Standards IEC 60079-0:2017 IEC 60079-11:2011 IEC 60079-31:2013 IEC 60079-7:2015/A1:2017 Note For expanded technical data regarding e.g. storage capacity and reliability refer to the BPC3200-* manual.
  • Page 19: Dimensions And Nameplates

    VisuNet FLX Panel Product Description Dimensions and Nameplates Dimensions Figure 3.2 21.5" dimensions 485.7 Figure 3.3 19" dimensions Figure 3.4 15" dimensions...
  • Page 20 VisuNet FLX Panel Product Description Note For further information on the System dimensions refer to the VisuNet FLX System manual. Nameplates and Labels The following nameplates and labels are attached to the VisuNet FLX Panel: Figure 3.5 Overview of the attached labels and nameplates (1) Main label Figure 3.6...
  • Page 21 VisuNet FLX Panel Product Description (2) Sublabel BPC3200-* Figure 3.7 (3) Equipotential Bonding Figure 3.8 (4) Sublabel DPU3200-* Figure 3.9...
  • Page 22: Mechanical Installation

    Scratches in the DPU screen weaken the glass structure. If the surface is damaged in any way, return the DPU to Pepperl+Fuchs at once and replace it with a new one. See chapter 7.2 for information about removing the DPU.
  • Page 23: Panel Installation

    Explosion protection is no longer ensured if a system with damaged seals is used. NEVER use a system with damaged seals in a hazardous area. If the seal is damaged in any way, return the system to Pepperl+Fuchs at once and replace it with a new one.
  • Page 24: General Installation Information

    VisuNet FLX Panel Mechanical Installation General Installation Information Observe the following requirements when installing the system components: • The equipment must be installed by competent personnel in accordance with the instruc- tions. National laws and regulations must be observed. • The building installation must provide a 20 A overcurrent protection.
  • Page 25: Mounting The Panel In The Enclosure

    VisuNet FLX Panel Mechanical Installation Mounting the Panel in the enclosure Warning! Risk of injury! Lifting the device on your own may lead to injury. Do not attempt to lift the device on your own. Use a crane or have another person help you. Overheating of the system can result in improper behavior of the software.
  • Page 26 VisuNet FLX Panel Mechanical Installation Space Requirements Circulation of air To ensure adequate ventilation of the Panel, leave enough space around the Panel for air circu- lation. Mount the Panel PC so that the spacing on the top, bottom, and sides is as follows: Side view Front view x1 >...
  • Page 27 VisuNet FLX Panel Mechanical Installation Installing the Panel within an enclosure with the Panel Mount Kit Cut a hole in the enclosure according to the dimensions of the selected display. Figure 4.3 Figure 4.4 Panel Mount Display Size Cutout width Cutout height Tolerance 21.5 "...
  • Page 28 VisuNet FLX Panel Mechanical Installation Figure 4.5 From the front, place the bottom edge of VisuNet FLX Panel in the opening. Tilt the top of the VisuNet FLX panel through the opening until the gasket connects smoothly to the enclosure. Ensure that the gasket is properly positioned in the groove and against the panel.
  • Page 29 VisuNet FLX Panel Mechanical Installation Installing the Panel using the drilling pattern Warning! Wall panel thickness! For the following installation a wall panel thickness of minimum 2 mm and max- imum 4 mm is required for correct mounting. For this installation no additional sales item is required. Not included in Panel Mount delivery but required: 21.5"...
  • Page 30 VisuNet FLX Panel Mechanical Installation Figure 4.7 19" FLX Panel Mount Figure 4.8 15.6" FLX Panel Mount...
  • Page 31: Electrical Installation

    VisuNet FLX Panel Electrical Installation Electrical Installation Warning! Danger of explosion! Cable insulation may become damaged if cables and connection lines are not used in ade- quate temperature ranges. Thus, short circuits within the cable may occur which in turn may give rise to sparks and/or surface temperatures capable of triggering an ignition.
  • Page 32: Equipotential Bonding Of The Visunet Flx Panel

    VisuNet FLX Panel Electrical Installation Equipotential Bonding of the VisuNet FLX Panel The VisuNet FLX is shipped with the following PB protective (equipotential) bonding wiring connection, if the panel mount option is selected: Warning! PB protective equipotential bonding! PB protective equipotential bonding is mandatory. PB wire from the computing platform housing PB stud to the pan head screw of the panel (1).
  • Page 33: Power Connection

    VisuNet FLX Panel Electrical Installation If you replace the DPU, reestablish the PB connection in the same configuration. Tighten the PB hardware to 4.0 Nm and build up the equipotential bonding stackup as shown in the picture: Figure 5.2 Power Connection Warning! Hazard due to excessive current! Excessive current can cause overloading of the electronics which could then result in injury or...
  • Page 34 VisuNet FLX Panel Electrical Installation Wiring and Connecting the Terminal Block Field Input A three-position, screw-type connector (MC311-500) is provided for connecting power to the VisuNet FLX panel. Figure 5.3 Power connector is included in the delivery. Connect a power source to the included power connector. This connector supports wire size 4 mm (~12-24 AWG).
  • Page 35: Interfaces

    VisuNet FLX Panel Interfaces Interfaces Caution! Damage to the electronics! The electronics can be damaged if plug-in connections are connected or disconnected while power is still being applied. Make sure that no power is being applied while connecting and disconnecting cables! Warning! Interfaces must have a strain relief in Ex-operation.
  • Page 36: Maintenance

    VisuNet FLX Panel Maintenance Maintenance All VisuNet FLX models perform a degree of thermal management to avoid overheating under heavy load. Note Operating temperature has influence on the VisuNet FLX lifetime. Caution! Use only approved spare parts. The installation of spare parts not intended for the VisuNet FLX may damage the device, machine or system.
  • Page 37: Exchanging The Bpc3200-* Or Dmu3200

    VisuNet FLX Panel Maintenance Exchanging the BPC3200-* or DMU3200-* Procedure If repairs or updates are required, the computing unit can be dismounted from the DPU and be replaced. Remove the panel if required. Place the unit on a soft, raised surface so that the front will not be damaged.
  • Page 38 VisuNet FLX Panel Maintenance Remove the pins (USB-Touchscreen signal, LVDS-video signal and Inverter LCD backlight) from the sockets of the DPU. Make sure to pull all the side tabs of the connectors evenly and smooth. Note Make sure to pull the side tabs of the connectors. Pulling on the wires can cause the pins to be removed from the connectors, especially with small wires and contacts that are found on the LVDS cable.
  • Page 39 VisuNet FLX Panel Maintenance Figure 7.5 Remove connectors [2] Figure 7.6 Remove the four screws that connect the computing unit to the DPU and remove the old computer unit from the DPU. Now the steps continue with your new device. If you are exchanging a BPC3200-*, open the side cover first.
  • Page 40 VisuNet FLX Panel Maintenance These installation steps are only relevant when installing a new BPC3200-*: To configure the screen resolution set your DIP switches correctly (Refer to the BPC3200-* manual for detailed information on the DIP switch positions.) In case you want to operate the serial interface ports in any other mode than RS-232 configure your serial ports by setting your Jumpers correctly and adjusting the settings in BIOS.
  • Page 41: Dismounting The Display Unit

    VisuNet FLX Panel Maintenance Figure 7.8 Close the cover of the computing unit If required mount your VisuNet FLX panel. Dismounting the Display Unit If repairs are required, the DPU can be dismounted from the BPC3200-* / DMU and be replaced. Uninstall the Panel from the enclosure.
  • Page 42: Gloves Tested For Touch Sensitivity

    Mounting holes for fixing the safety lines for System installation Gloves Tested for Touch Sensitivity This section lists selected gloves and their touch sensitivity with the capacitive touch screen. This test was conducted by Pepperl+Fuchs. Warning! It is the end user's responsibility to choose appropriate gloves.
  • Page 43: Cleaning

    The display unit consists of a chemically strengthened front glass and an optional stainless steel bezel. The chemical resistance of the sealant between the glass and bezel was specified by the sealant manufacturer. Pepperl+Fuchs also tested the resistance of the sealant and the resistance of the gasket between the bezel and the housing.
  • Page 44: Accessories

    VisuNet FLX Panel Accessories Accessories Replacement Components Item No. Type Code Description 70128300 DPU3200-22GT-304A-V1-N0 Display Unit 21,5" Display (Full HD) Display option "22GT" with capacitive touch screen 70128301 DPU3200-22FC-304A-V1-N0 Display Unit 21,5" Display (Full HD), optically bonded Display option "22FC" with capacitive touch screen Needs to be BPC3200-*...
  • Page 45 Pepperl+Fuchs Quality Download our latest policy here: www.pepperl-fuchs.com/quality www.pepperl-fuchs.com © Pepperl+Fuchs · Subject to modifications Printed in Germany / DOCT-7136...