TDP05K Refer to the Ruskin.com website for the most up-to-date version of this document. Document Introduction............4 Navigating the Start-Up Menu .
Navigating the Start-Up Menu After installing the TDP05K Airflow Measuring System, power on the unit. Menu options appear on the front panel LCD display of the primary controller and are replicated on the remote user interface (see Figure 1). The LCD dis- play has a 16 character per line, 2-line display.
Configuration The onboard microprocessor in the TDP05K primary probe allows for system configuration, operating parameter selection, analog output configuration, and display filtering. The primary probe is the automation interface and also acts as a primary across a wired network to other ancillary probes (up to 15) and the remote display when that option is selected.
MENU and UP or DOWN until the arrow is next to Operator Menu. 2. Press ENTER to enter the Operator Menu submenu options. a. If the Operator PIN is enabled, the LCD screen displays the following message: TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 7
BACnet Flow Alarm Configures high and low setpoints, deadband, and alarm delay settings and turns the BACnet Configuration flow high and low alarms on and off. (Flow Alarm Cfg) TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 8
Configures high and low setpoints, deadband, and alarm delay settings and turns the BACnet Alarm Configuration temperature high and low alarms on and off. (Temp Alarm Cfg) Exit Operator Menu Returns the display to normal operation. (Exit Oper Menu) TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Alternatively, press ESC to return to the Operator Menu without updating the PIN. Note: If the PIN settings are enabled, the PIN number must be entered each time the Operator Menu is entered. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
ESC or ENTER DOWN Returns to Exit this Menu Operator Menu DOWN ENTER 1. Duct Area controls area input when the Other duct shape is selected. Figure 3: Flow Configuration Flowchart TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 11
Actual Liters Per Minute ALPM Actual Cubic Meters Per Hour ACMH Standard Cubic Feet Per Second ACFS SCFM Standard Cubic Feet Per Minute Standard Cubic Feet Per Hour SCFH TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 12
The standard conditions for Standard Cubic Feet Per Minute airflow measurements are as follows: 14.696 pounds per square inch (psia) equals 101.325 kPa at sea level. 70 degrees Fahrenheit equals 15.6 degrees Celsius. 50% relative humidity (RH). TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Select between System Flow and Custom Text for text appearing in line 2 of the display Line 2 Custom Select up to seven ASCII characters to display in line 2 of the display. See Selecting Custom Text for more information. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
3. Scroll through the submenu options and make any necessary updates. See Table 5 for a description of the Display Configuration submenu selection options and their configurable options. Selecting Custom Text 1. Scroll to the Line 2 Custom submenu and press ENTER. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
The Analog Output 1 Parameters submenu is used to select the process variables that Output 1 represents. Available process variables include flow, temperature, and none. If flow is selected, the output represents the defined flow design range. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 16
2. Press ENTER. 3. Make any necessary updates to the submenu selection. See Table 6 for a description of the Analog Output 1 submenu selection option and its configurable option. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
2. Press ENTER. 3. Make any necessary updates to the submenu selection. See Table 7 for a description of the Analog Output 2 submenu selection option and its configurable option. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
2. Press ENTER. 3. Make any necessary updates to the submenu selection. See Table 8 for a description of the Temperature Output LPF submenu selection option and its configurable option. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
2. Press ENTER. 3. Make any necessary updates to the submenu selection option. See Table 9 for a description of the Flow Output LPF submenu selection option and its configurable option. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Design Range ENTER High DOWN Temperature ENTER Range Low DOWN Temperature ENTER Range High DOWN Returns to Exit this Menu Operator Menu DOWN ENTER Figure 10: Analog Output Calibration Flowchart TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Select between -34.6 to 129.2°F (-37 to 54°C) for maximum range of output temperature spanning Note: By default, the TDP05K Airflow Measuring System is factory calibrated. Calibrating the Analog Output To calibrate the analog output with the primary probe mounted in its operating location or in a calibration lab: 1.
Page 22
5. Connect a digital multi-meter set to scale Analog Output 1 across terminals 1 and 2 on the TDP05K Airflow Measuring System. See Figure 11 for terminal locations. PRIMARY Reset Boot Probe Network BACNET Switch 3 on...
Page 23
17. Scroll through the submenu options and make any necessary updates. See Table 10 for a description of the Analog Output Calibration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
3. Scroll through the submenu options and make any necessary updates. See Table 11 for a description of the Temperature Balance Configuration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Only when # of Data Points is set to 2 or higher. Operator Menu DOWN Only when # of Data Points is set to 3. Figure 13: K-Factor Configuration Flowchart TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
2. Press ENTER to view the K-Factor Configuration submenu. Scroll to the K-Factor Enable? submenu selection. 3. Press ENTER. The display indicates the current K-Factor setting (Off or On). TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
5. Press ENTER to adjust the manual K-Factor gain. Press UP or DOWN to modify the currently selected value. 6. Press ENTER to confirm the value and return to the K-Factor Configuration submenu. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Allow the system at least 60 seconds after a velocity state change to balance the displayed readings. 6. The display returns to the K-Factor Configuration submenu. Scroll to the Point 1 Velocity submenu selection. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 29
When two data points are selected, the display indicates the K-Factor Generated, Calculated Offset 1, and Calculated Gain 1 screens. When three data points are selected, all five screens display. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 30
14. Press UP or DOWN to scroll through the submenu options and make any necessary updates. See Table 12 for a description of the K-Factor Configuration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
2. Press ENTER. 3. Make any necessary updates to the submenu selection. See Table 13 for a description of the Menu Timeout submenu selection option and its configurable option. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Select a value between 1 and 127. Holding down the button increases the rate the value updates. BACnet Baud Rate Select the 9,600, 19,200, 38,400 (default), or 76,800 baud rate. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 33
3. Scroll through the submenu options and make any necessary updates. See Table 14 for a description of the BACnet Network Configuration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Choose a value the flow must go below for an alarm condition to exist. Alarm High Setpoint Choose a value the flow must surpass for an alarm condition to exist. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 35
3. Scroll through the submenu options and make any necessary updates. See Table 15 for a description of the BACnet Flow Alarm Configuration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Choose a value the temperature must go below for an alarm condition to exist. Alarm High Setpoint Choose a value the temperature must surpass for an alarm condition to exist. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 37
3. Scroll through the submenu options and make any necessary updates. See Table 16 for a description of the BACnet Temperature Alarm Configuration submenu selection options and their configurable options. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
It is also used to restore the device to a preinstallation state. 1. When the TDP05K Airflow Measuring System’s LCD screen displays the average temperature and average velocity or volume, press MENU and UP or DOWN until the arrow is next to the Supervisor Menu.
Alternatively, press ESC to return to the Supervisor Menu without updating the PIN. Note: If the PIN settings are enabled, the PIN number must be entered each time the Supervisor Menu is entered. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
DOWN Disable Sensors ENTER DOWN Display Probe ENTER Status DOWN Display Probe ENTER Data DOWN Exit this Menu Returns to Operator Menu DOWN ENTER Figure 19: Sensor Management Flowchart TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 41
3. Press ENTER. The display indicates the number of active probes and sensors. In this example, one probe is active and enabled and two out of two sensors are valid and enabled. 4. Press ESC or ENTER to return to the Sensor Management submenu. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 42
13. Press UP or DOWN to scroll to the Enable Sensors submenu selection. Press ENTER. 14. Scroll to display the correct probe number on line 2 and press ENTER. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 43
(1 through 8). Press ESC to return to the Probe Data screen. 23. Press UP or DOWN to scroll the menu display to the remaining probes, or press ESC to return to the Sensor Management menu. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Primary probe returns to normal operation. 1. In the Supervisor Menu, press UP or DOWN to scroll to the Reset Sensors submenu. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 45
2. Press ENTER. The display indicates: The primary probe automatically resets all the sensors and devices and then restarts. After warming up, the primary probe returns to the normal operation mode. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Perform a local sensor scan and re-enable local sensors to get an inventory from the probe network. Display returns to normal operation and factory-default settings are restored. 1. In the Supervisor Menu, press UP or DOWN to scroll to the Factory Default submenu. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Page 47
The primary probe automatically resets all the sensors and devices and then restarts. After warming up, it returns to the normal operation mode. All settings are restored to their factory-default state. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Ruskin—CONFIDENTIAL...
Factory calibration of thermal dispersion components of the assembly shall be lead-free RoHS compliant. The information provided in this manual is believed to be complete and accurate. Ruskin Manufacturing is a sensors shall be at 25 points between 0 and 5,000 FPM using NIST...