Air Quality Solutions
Installation & Maintenance Manual
Primary
Ancillary
Remote Display
Model: TDP05K
Advanced Thermal Dispersion Airflow
& Temperature Measuring Probe
ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE OR OBLIGATION © Ruskin October 2019
II-TDP05K-1019/Replaces II-TDP05K-1218

Advertisement

loading
Need help?

Need help?

Do you have a question about the TDP05K and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ruskin TDP05K

  • Page 1 Air Quality Solutions Installation & Maintenance Manual Primary Ancillary Remote Display Model: TDP05K Advanced Thermal Dispersion Airflow & Temperature Measuring Probe ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE OR OBLIGATION © Ruskin October 2019 II-TDP05K-1019/Replaces II-TDP05K-1218...
  • Page 2 The TDP05K may be used in rectangular, oval, or round applications when installed in accordance with this instal- lation manual. The TDP05K is designed to be installed in almost any location that airflow needs to be measured. Measurements may be improved by following the placement guidelines in this document. When adequate space is not available, more probes and/or sensors are recommended.
  • Page 3 Probe Airflow Measuring Issued June 30, 2009 The sensor density is based on extensive lab testing to optimize the accuracy of the TDP05K Airflow Measuring System. When installing the thermal dispersion probes, use the Rectangular Duct Mounting, Round Duct Mounting, and Oval Duct Mounting sections to determine the proper spacing between each probe within the opening.
  • Page 4 Remote Wired Primary Table 1: Number of Probes/Sensors per Probe for Rectangular Duct Applications (Part 1 of 2) The TDP05K Airflow Measuring Station can be ordered with a Remote Wired Primary (included with the HTDP-S) as Duct Duct Width, in. (mm)
  • Page 5 Automation System. Spacing of Internal mount probes is the same as Insertion mount probes. ANCILLARY VIEW ANCILLARY VIEW TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions 60°...
  • Page 6 (304 mm), use the same number of probes and sensors as the 12 inches (304 mm) size. 48 (1,219) Figure 6 TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions Table 2: Number of Probes/Sensors per Probe for Round Duct Applications 60 (1,524)
  • Page 7 Note: The primary probe is the longest probe for oval mounting. It should be installed in the most accessible location for the application. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 8 H 1/5 H 1/7 2. See Figure 11 for details. 2. See Figure 10 for details. (2,134) (2,057) V 2/4 TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions Ruskin—CONFIDENTIAL...
  • Page 9 Minimum Mounting Distances & TEMPERATURE MEASURING PROBE Figure 12 represents applications for which the TDP05K Airflow Measuring System is most suitable. If your Figures 11a and 11b represent applications for which the Advanced Thermal Dispersion Airflow Measuring System particular application is not shown or if you do not have the space to observe the minimum distance, more is most suitable.
  • Page 10 Minimum Mounting Distances Minimum Mounting Distances Figure 12 represents applications for which the TDP05K Airflow Measuring System is most suitable. If your Figure 11b represents applications for which the Advanced Thermal Dispersion Airflow Measuring System is most particular application is not shown or if you do not have the space to observe the minimum distance, more suitable.
  • Page 11 Double-check the hole locations before proceeding to the next step. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions On the side of the duct where the box will be located, drill 2 1/4 in. (57 mm) holes at the correct heights to 3.
  • Page 12 IMPORTANT: Install the probes with the mounting plates square and without twisting or bending. See the primary probe wiring section to complete wiring. Figure 13a: Internal Mount Ancillary Probe NEMA 1 or NEMA 4X enclosure 10’ Standard factory wire terminated at probe end TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 13 Wires in an exposed or conduit installation must meet the wiring minimum bend radius of 1.5 in. (38 mm). bend radius is 1.5 in. (38 mm). Figure 14a: Minimum Ben Radius TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 14 Sample Wiring Configuration 2. Connect the BACnet® output (A- and B+) from the primary probe to a BACnet network. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions Ruskin—CONFIDENTIAL...
  • Page 15 Figure 14c 24VAC Primary Bare  Silver White Black Black Ancillary Bare  Silver Black White Black Ancillary TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 16 2. Connect the BACnet® output (A- and B+) from the primary probe to a BACnet network. Note: The two A- connections and the two B+ connections are electrically identical.” TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions Ruskin—CONFIDENTIAL...
  • Page 17 3. Connect additional probes in a daisy-chain series. the TDP05K Airflow Measuring System is the end of line in the BACnet network, set the BACnet switch to 1 ON network (switch 3 [see Figure 16]). If the primary probe output is connected to a BACnet network interface and 3.
  • Page 18 Connect the 24 AWG black wire from the primary probe terminal labeled Probe Network D- to the remote d. If the remote display in each TDP05K Airflow Measuring System is the end of line on the probe network, b. Connect the 24 AWG black wire from the primary probe terminal labeled Probe Network D- to the remote display terminal labeled Probe Network D-.
  • Page 19 Refer to the TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Refer to the TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Refer to the TDP05K Advanced Thermal Dispersion Probe Air Flow Measuring System Technical Bulletin (LIT-12012477) for detailed configuration instructions.
  • Page 20 Menu Structure Refer to the TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin Refer to the TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin (LIT-12012477) for detailed configuration instructions. http://www.ruskin.com/catalog/servefile/id/6767 for detailed configuration instructions.
  • Page 21 Enables PIN protection for the Supervisor Menu (Enable Supv PIN) Change Supervisor PIN Allows the user to update the PIN (Change Supv PIN) TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions Ruskin—CONFIDENTIAL...
  • Page 22: Troubleshooting

    Look at drawings and make sure left and right are not incorrect point or wrong con- No BACnet communication swapped. nector. with the BAS Verify configuration parameters match what is required Not configured correctly. to communicate with the BAS. TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Installation Instructions...
  • Page 23: Replacement Parts

    Follow these steps if direct inspection via other means is not possible and the probes must be removed: 1. Before cleaning the sensors, make sure the power to the TDP05K Airflow Measuring System is turned off or Before cleaning the sensors, make sure the power to the Advanced Thermal Dispersion Airflow Measuring 1.
  • Page 24: Technical Specifications

    Factory calibration of thermal dispersion components of the assembly shall be lead-free RoHS compliant. binding in detail. In keeping with its policy of continuous improvement, Ruskin reserves the right to change or modify designs or specifications resistant construction. Factory calibration of thermal dispersion components of the assembly shall be lead-free RoHS compliant.