Fault Finding - Extinguishing Control Unit Faults; Extinguishing Control Unit General Faults; Indications; Possible Causes - GE Ziton ZP3-ECU Maintenance Manual

Extinguishing control unit
Table of Contents

Advertisement

ZP3-ECU Maintenance Manual

Fault Finding - Extinguishing Control Unit Faults

Extinguishing Control Unit General Faults

There are a number of faults identified by the control panel as a general fault on the
extinguishing control unit.

Indications

Panel buzzer sounds.
Display indicates a fault as GNFLT, for example:
GNFLT
Zone 001 Dev 5002
Carbon dioxide ECU storage room
Events are printed (if printer configured).
Appropriate red Zone LED illuminates to indicate the zone in which the fault occurred.

Possible Causes

A fault on the control system falls into one of the following categories:
Manual Extinguishant Release Faults.
Extinguishant Actuation Faults.
Extinguishant Pressure Faults.
Fire Bell Fault.
Extinguishant Discharge Siren Fault.

Corrective Actions

1. Press the ACCEPT button to accept the fault.
2. Refer to the paragraphs below with regard to the type of fault displayed.
3. Reset the panel.
Issue 1 (01/08/2006)
Event 012
Doc. No. 503-0800ZE-M-01
Page 11