Watlow F4T Installation And Troubleshooting User’s Manual page 37

Hide thumbs Also See for F4T:
Table of Contents

Advertisement

Indication
Alarm Low
Sensor input below
low alarm set point
Alarm High
Sensor input above
high alarm set point
Error Input
Sensor does not
provide a valid sig-
nal to controller
Limit won't
Limit will not clear
clear or reset
or reset with key-
pad or digital input
Limit Error
Limit state cannot
be determined due
to lack of sensor
input, limit will trip
Limit Low
Sensor input below
low limit set point
Watl o w F 4T I nst al l & Tr o u bl es h o o tin g
Anderson-Bolds ~ 216-360-9800
Description
• Temperature is less than
alarm set point
• Alarm is set to latching
and an alarm occurred in
the past
• Incorrect alarm set point
• Incorrect alarm source
• Temperature is greater
than alarm set point
• Alarm is set to latching
and an alarm occurred in
the past
• Incorrect alarm set point
• Incorrect alarm source
• Sensor improperly wired
or open
• Incorrect setting of sen-
sor type
• Calibration corrupt
• Sensor input is out of
limit set point range
• Limit set point is incor-
rect
• Digital input function is
incorrect
• Sensor improperly wired
or open
• Incorrect setting of sen-
sor type
• Calibration corrupt
• Temperature is less than
limit set point
• Limit outputs latch and
require reset
• Incorrect alarm set point
www.anderson-bolds.com
Possible Cause(s)
3 4
Corrective Action
• Check cause of under
temperature
• Clear latched alarm
• Establish correct alarm
set point
• Set alarm source to
proper setting
• Check cause of over
temperature
• Clear latched alarm
• Establish correct alarm
set point
• Set alarm source to
proper setting
• Correct wiring or re-
place sensor
• Match setting to sensor
used
• Check calibration of
controller
• Correct cause of sensor
input out of limit range
• Set limit set point to
correct trip point
• Set digital input func-
tion and source instance
• Correct wiring or re-
place sensor
• Match setting to sensor
used
• Check calibration of
controller
• Check cause of under
temperature
• Clear limit
• Establish correct limit
set point
Chapter 5 Troubl eshooti ng

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D4t

Table of Contents