Download Print this page

Advertisement

Quick Links

XP95 Sounder VAD Base
FUNC TION
The XP95® Sounder Visual Alarm Device (VAD)
Bases incorporates a standard mouting base
with a loop-powered sounder VAD. It is used to
signal a fire alarm in enclosed areas.
The XP95 Sounder VAD Base can be used either
with a detector fitted or with a cap for operation
as a stand-alone alarm device. The XP95
Sounder VAD Bases are supplied with a built-in
isolator.
FEATURES
The product offers:
Two volume ranges 55–75dB(A) and
75–91dB(A)
EN54-23 Compliant Category O. VAD
EN54-3 Compliant Sounder
VAD flash rate of 0.5Hz
Synchronisation of 'alert' and 'evacuate'
tones
Individual and group addressing
MANAGEMENT
SYSTEMS
Assessed to ISO 9001:2008
Certificate No. 010
LPCB Cert No. 010
See www.RedBookLive.com
Apollo Fire Detectors Limited 2016
©
36 Brookside Road, Havant,
Hampshire, PO9 1JR, UK.
MANAGEMENT
SYSTEMS
Overseas offices: America China Germany
Assessed to ISO 14001:2004
Certificate number EMS 010
Part no 45681-705 - XP95 Sounder VAD Base
with Isolator
Unique acoustic self-test
Unique VAD self-test
Built in Isolator
Complies with NEN2575 (45681-706),
DIN0833 and DIN33404 (45681-707)
Tel: +44 (0)23 9249 2412
Fax: +44 (0)23 9249 2754
PP2478/2016/Issue 5
Email: sales@apollo-fire.com
Web: www.apollo-fire.co.uk

Advertisement

loading

Summary of Contents for Apollo XP95

  • Page 1 VAD. It is used to signal a fire alarm in enclosed areas. The XP95 Sounder VAD Base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device. The XP95 Sounder VAD Bases are supplied with a built-in isolator.
  • Page 2: Electrical Considerations

    3 (= Sounder and VAD fault) is transmitted on the next polling. ADDRESSING The XP95 Sounder VAD Base responds to its This feature can also be used during own individual address set with a DIL switch. commissioning or periodical maintenance It also responds both to a group address, set testing.
  • Page 3: Mechanical Construction

    Low tone setting volume - nominally 50 to 65dB(A) Output Bits DIMENSIONS AND WEIGHT Group Mode Part no Description Dimension Alert Tone & Weight 45681-705 XP95 Sounder VAD 115 x Evacuate Tone Base with Isolator 38mm (white flash) 168g Interrupt 45681-706 XP95 Slow whoop...
  • Page 4: Dimensional Drawing

    3. The Sounder VAD Base is a Type A device, ie, for indoor use only. 4. The isolating circuit of the Sounder VAD Bases is certified to EN54–17. 5. For information on isolating circuits see publication PP2090 available on request from Apollo. DIMENSIONAL DRAWING...
  • Page 5 COVERAGE DIAGRAM XP95 SOUNDER VAD BASE - CROSS SECTION OF COVERAGE VOLUME. EACH SQUARE REPRESENTS 1M...

This manual is also suitable for:

45681-705