General
This guide describes the installation of the following base
Part number
45681-702
45681-292
45681-293
Connect the device only to control panels using the Discovery protocol.
Warning
The Discovery Sounder Base requires compatible fi re alarm panel software to operate.
Please check with the panel manufacturer before installation.
Function
The Discovery Sounder Base combines a sounder, a detector base and a short circuit isola-
tor in one unit. It has up to 15 tone pairs, 7 volume settings, independent control of sounder
and fast turn-on functions. The confi guration of the sounder is set by the control panel.
Please refer to the panel literature for details.
When the integral short circuit isolator operates, a yellow LED is visible through the
moulding opposite the XPERT card (see fi g 1.)
Note: The Discovery Sounder Base is not suitable for outdoor use.
Mounting Instructions
The Discovery Sounder Base may be secured to a UK standard conduit box or surface
mounted (providing there is access through the surface for cabling). If a detector is fi tted,
lock it if required by screwing in the grub screw in the detector with a 1.5mm hex driver
(part no 29600-095).
Wiring Details
Note: This product is polarity sensitive (supply reversal protected) and will not function if
wired incorrectly.
Terminate all loop cables in the two way terminal blocks. Connect the incoming loop
cables to L1 IN (–) and L2 (+) and the outgoing cables to L1 OUT (–) and L2 (+). Functional
earth or screen may be connected to the EARTH connection.
When using as a stand-alone unit, a cap is available (red cap part no 45681-293 or white
cap part no 45681-292) and is secured with a 1.5mm AF hexagon socket head screw. A
hexagonal driver (part no 29600-095) is available from Apollo.
www.acornfiresecurity.com
Discovery
Sounder Base
®
Installation Guide
Product Description
Discovery Sounder Base (White) with isolator
White Cap only (Lockable)
Red Cap only (Lockable)
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Discovery 45681-702 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Apollo Discovery 45681-702

  • Page 1 When using as a stand-alone unit, a cap is available (red cap part no 45681-293 or white cap part no 45681-292) and is secured with a 1.5mm AF hexagon socket head screw. A hexagonal driver (part no 29600-095) is available from Apollo. www.acornfiresecurity.com...
  • Page 2 Tone Table Remote LED Address –R setting L1 IN L1 OUT – – EARTH Position of Isolator LED © Apollo Fire Detectors Limited 2004–2007/JDR/JLC/JDR/JLC/TP Fig. 1 Discovery Sounder Base with isolator wiring www.acornfiresecurity.com...
  • Page 3 www.acornfiresecurity.com Fault Finding Address Setting The address of the Discovery Sounder Base is set using segments 1-7 of the DIL switch and Problem Possible Cause are set to “0” (ON) or “1”, using a small screwdriver or similar tool. A complete list of address No response or missing Incorrect address setting settings is shown below.
  • Page 4 www.acornfiresecurity.com XPERT Card Addressing Commissioning Select the desired address for the detector and remove the pips indicated in black. Remove It is important that the device be fully tested after installation. Many fault conditions are the pips with a small screwdriver. result of simple wiring errors.