I/O RANGING & FINE ADJUSTMENTS
After the DIP SW setting is complete, set up the precise input and output range using the front control buttons. Be sure that
the front control button function is enabled with the DIP switch setting.
The front LEDs' colors and blinking patterns help you to easily identify the transmitter's status and confirm the setup actions
in each step of Calibration Modes. Please read the following explanations referring to "Calibration Flow Chart".
PREPARATION (e.g. M3LV-R4/A)
1) Mount the DIP-SW-configured M3LV on to a DIN rail.
2) Connect the M3LV to a simulator and a multimeter and to a
DC power source as shown below.
3) Turn the power supply on and wait for 10 minutes.
■ CALIBRATION FLOW CHART
LD1*
G
Fine Adjustments ?
LD2
LD3
G
HOLD DOWN
1 – 2 s
MODE
LD1
R
FINE ZERO
LD2
ADJUSTMENT MODE
G
LD3
or
UP
DOWN
HOLD DOWN
approx. 2 s
MODE
LD1
R
FINE SPAN
LD2
ADJUSTMENT MODE
LD3
or
UP
DOWN
G
HOLD DOWN
approx. 2 s
MODE
LD1*
G
LD2
LD3
POWER ON
I/O Ranging ?
RUN MODE
HOLD DOWN
Once the transmitter
LD1
enters the fine zero
R
adjustment mode,
LD2
the output goes to
R
preadjusted 0%
value regardless
LD3
of the present input
signal.
HOLD DOWN
Once the transmitter
LD1
enters the fine span
R
adjustment mode,
LD2
the output goes to
preadjusted 100%
value regardless
LD3
of the present input
R
signal.
HOLD DOWN
RUN MODE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Simulator
+
Example with Volt input.
See Connection Diagram
for other input types.
MODE
Control
UP
Buttons
DOWN
> 5 s
MODE
Apply simulated 0% input signal.
HOLD DOWN
INPUT
RANGING
MODE
HOLD DOWN
Apply simulated 100% input signal.
approx. 2 s
MODE
Adjust simulated input until the output meter
shows desired 0% output.
HOLD DOWN
OUTPUT
RANGING
MODE
HOLD DOWN
Adjust simulated input until the output meter
shows desired 100% output.
approx. 2 s
MODE
When you set 0% or 100% input/output ranges,
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off,
which indicates the setup is complete.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range.
* For the model M3LV-x/A, the green LED is blinking.
For the model M3LV-x/B, the green LED turns on.
M3LV
Multimeter
2
7
3
8
DC Power Source
11
+ –
12
A
Amber LED
OFF
G
Green LED
ON
Red LED
Blink
R
0% INPUT
DOWN
CONFIGURED
100% INPUT
UP
CONFIGURED
0% OUTPUT
DOWN
CONFIGURED
100% OUTPUT
UP
CONFIGURED
EM-2660-A Rev.2 P. 5 / 7