Minimum/Maximum Setpoint, Out-of-Range

and Continuous Flow
Minimum Setpoint Settings: 32°F ( 0 °C), 68°F (2 0° C) or
-20° F (-29° C)
Maximum Setpoint Settings: 68°F (20° C) or 86° F (30° C)
Out-of-Range Settings: 1.8, 3.6 or 5.4°F ( 1, 2 or 3°C)
Continuous Airflow Settings: F/ON or F/OFF
3
2
1. Turn unit on. Press and hold + (plus) key.
2. Press and hold - (minus) key.
3. Press and hold Defrost key.
4. Check that the ! light flashes green.
5. The operator can select a minimum setpoint. Press+
(plus) key or - (minus) key to change setting.
6. Press SET key to save setting. Maximum Setpoint
setting will appear next.
7. Press + (plus) key to increase Maximum Setpoint
setting. Press - (minus) key to decrease setting.
8. Press SET key to save Maximum Setpoint setting.
9. Next setting is Out-of-Range. Press + (plus) key to
increase Out-of-Range setting. Press - (minus) key to
decrease setting.
10. Continuous Airflow determines whether the evaporator
fan is on or off at setpoint. Press + (plus) or - (minus) key
to select the desired operating mode. Press the SET key
to save fan mode setting.