In-line ecm circul ating pumps

Advertisement

Quick Links

I N - LI N E ECM CI RCU L ATI N G PU M P S
S55 , 57, 69 AN D H 53 , 5 4 , 6 3 TO H67
A N D O P E R AT I N G I N S T R U C T I O N S
1.0 installation
2.0 system cleanliness
3.0 starting up
4 .0 electrical wiring
5.0 speed setting
caution
Always disconnect power supply from motor
before servicing.
1.0 installation
For convenience, Armstrong circulators generally are installed
in vertical pipelines, but may be changed easily on the job for
horizontal pipelines or for opposite flow directions. To make the
change, remove the body capscrews, taking care body gasket is
kept in position, and rotate body to desired direction at 90° or
180° from the original position.
With the arrow on the body pointing in direction of the flow,
insert body capscrews and tighten evenly. On models s55 and
s57 a gap between the bearing bracket and pump body (vo-
lute) is normal. Do no over tighten body capscrews! Turn pump
shaft manually at coupler to make sure shaft turns freely and
impeller does not rub in body. Always install with motor shaft
in a horizontal position. For non maintenance free models the
oil cups or oil well cover must be facing up.
All ecm models are shipped for upward discharge as pumps of
this size usually are installed in an upward direction on hydronic
systems, so the point of zero pressure change - namely, the
compression tank connection - can be made easily to the sys-
tem on the suction side of the circulator.
The pump should be installed in a position to permit proper
lubrication and servicing. Motor and bearing brackets are to be
kept free of insulation. Pump and motor unit are designed to be
supported by the in-line piping only. Do not support in any oth-
er manner. A height of approximately four feet above the floor
is recommended. When placing the pump between flanges,
tighten flange bolts evenly and do not tighten excessively.
Gate valves should be installed on the discharge and suction
side of the pump to facilitate service. On larger pump sizes, a
check valve should be located on the discharge side of pump
between the pump body and the gate valve to prevent damage
due to water hammer.
|
I N S TA L L AT I O N
6.0 0v to 10v dc control
1
7.0 lubrication
1
8.0 seal replacement
1
9.0 appendix 1
1
2
2.0 system cleanliness
Before starting the pump, the system must be thoroughly
cleaned, flushed and drained, then replenished with clean
liquid. Welding slag and other foreign materials, 'stopleak'
and cleaning compounds, excessive or improper water treat-
ment - all are detrimental to the pump. Warranty will be void if
any of these conditions are allowed to exist. (Refer to File no.
6090.645 design and care of closed hydronic systems.)
3 .0 starting up
The pump must be fully primed on start-up. Fill system piping
and pump body with liquid and vent complete system, turning
pump by hand to dislodge air from body. Make sure fittings and
drain valves are airtight, then add any additional fill required.
Check motor against available electric supply, then start pump
making sure rotation is correct. When viewed from motor end,
rotation is clockwise. If pressure does not develop, stop pump,
re-check, vent and fill. Never attempt to fill the system when
the pump is running.
note: ecm motors have a 15 second soft start-up time once plugged in,
and a 30 second time to achieve full speed (thus different from standard
induction motors)
4 .0 electrical wiring
1 Electrical installation should be conducted by a qualified
electrician. Installers should be equipped with proper
personal protective equipment.
2 Always make sure the electric power is disconnected and
locked out before wiring the circulator.
|
MO DEL S
The electrical wiring must be installed in strict ac-
cordance with the Canadian Electrical Code (Canada)
or the U.S. National Electrical Code (USA),or bs767 1
(Europe) as well as local codes and regulations.
File No: 10.791
Date: june 17, 2019
Supersedes: 10.791
Date: april 6, 2018
2
2
2
3

Advertisement

loading

Summary of Contents for Armstrong S55

  • Page 1 File No: 10.791 MO DEL S Date: june 17, 2019 S55 , 57, 69 AN D H 53 , 5 4 , 6 3 TO H67 Supersedes: 10.791 I N S TA L L AT I O N Date: april 6, 2018 A N D O P E R AT I N G I N S T R U C T I O N S 1.0 installation...
  • Page 2: Speed Setting

    i n stal l a t io n & In-line circulating o p era t ing i nstruct ion s pumps 115V or 208-230V 1ph wiring - see At the start of each following heating season, lubricate with connections Appendix 1 for more details sae 30 oil.
  • Page 3 In-line circulating i n sta l l a t i o n & pumps o per at i n g i n str uct i o n s caution warning Before operating pump, carefully check: Installation, operation, and maintenance must be 1 Is the pump primed? performed by qualified personnel.
  • Page 4 PerfectSpeed® User Interface. On power up the interface board ranges. extracts the operating parameters from the motor control. Parameter categories include: Table 2 – Armstrong centrifugal pump & motor operating • Motor direction parameters • Motor mode of operation Control mode...
  • Page 5 In-line circulating i n sta l l a t i o n & pumps o per at i n g i n str uct i o n s Input demand AC line connections There are two methods of setting the input demand using the Check to see if the line voltage matches the nameplate voltage.
  • Page 6: Troubleshooting

    i n stal l a t io n & In-line circulating o p era t ing i nstruct ion s pumps PerfectSpeed® motor and user interface Using 0 V to 10V DC signal Motor is not running If the PerfectSpeed® motor with User Interface isn’t running, perform the following checks: 1 Ensure that both the PerfectSpeed®...
  • Page 7 In-line circulating insta l l a t io n & pumps opera ting in str u ct io n s 3 glossary fig 1 connections The glossary contains definitions for acronyms and terms oc- green/verde screw curring in the Operation, Configuration, and Troubleshooting ground Manual or in the PerfectSpeed®...
  • Page 8: Appendix A: Motor Charts

    i nstal latio n & In-line circulating operati ng instruction s pumps Maximum Demand (%) The highest value of operation relating to motor limits as de- National Electric Code fined in the Motor Mode of Operation. It is represented as the nfpa upper limit of the Y-axis in the Motor Profile graph.
  • Page 9 In-line circulating insta l l a t io n & pumps opera ting in str u ct io n s...
  • Page 10 t o r o n t o 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291 b u f f a l o 93 east avenue north tonawanda, new york u.s.a. 14120 -6594 +1 716 693 8813 b i r m i n g h a m heywood wharf, mucklow hill halesowen, west midlands...

This manual is also suitable for:

S57S69H53H54H63H67