GENERAL DATA

Base Rooftop DOAS
Table 1: Base Rooftop DOAS
Model No.
Design Airflow (CFM)
ESP (in. wg)
Entering Air Summer
DB/WB (°F)
Entering Air Winter DB (°F)
Cooling Performance
Coil LAT DB/WB (°F)
Total Cooling Capacity
(MBH)
Sensible Cooling Capacity
(MBH)
Hot Gas Reheat Coil
Capacity (MBH)
Evaporator coil depth
(rows)
Number of compressors
Compressor Type(s)
Heating
Fuel
Capacity Input (MBH)
Capacity Output (MBH)
LAT (°F)
Turndown Type
Turndown Ratio
Supply Fan Data
Fan Quantity
Wheel Speed (RPM)
Motor HP
Configuration
Outdoor Air Intake
Supply Air Discharge
Weight (lbs)
Filtration
Hood
Supply
Note:
 Capacity Data above may change if entering air temperatures, leaving air temperatures (LAT), or airflow rates are varied.
 Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable
regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
AR-DR02-03A
AR-DR02-04A
620
770
2.5
2.5
95/75
95/75
0
0
54.9/54.8
55.1/55.0
43.6
53.8
26.8
33.2
35.3
41.7
3
3
1
1
Inverter scroll
Inverter scroll
Natural Gas
Natural Gas
75
75
60
60
89.6
72.2
Modulating
Modulating
4:1
4:1
1
1
1900
1939
3/4
3/4
End
End
Bottom
Bottom
1,064
1,070
None
None
2" MERV 8
2" MERV 8
AR-DR02-05A
AR-DR02-06A
960
1,050
2.5
2.5
95/75
95/75
0
0
55.0/54.9
54.9/54.8
67.3
73.8
41.4
45.4
48.4
52.3
4
4
1
1
Inverter scroll
Inverter scroll
Natural Gas
Natural Gas
100
100
80
80
77.2
70.5
Modulating
Modulating
4:1
4:1
1
1
1991
2029
1
1
End
End
Bottom
Bottom
1,095
1,098
None
None
2" MERV 8
2" MERV 8
AR-DR02-07A
1,240
2.5
95/75
0
55/54.9
87.0
53.6
57.9
6
1
Inverter scroll
Natural Gas
150
120
89.6
Modulating
4:1
1
2113
1.5
End
Bottom
1,153
None
2" MERV 8

Hide quick links: