Sequence Of Operation; Start-Up / Standby; Heat Mode; Recovery From Lockout - LG GEN2 Series Installation And Operation Manual

Rooftop dedicated outdoor air systems
Table of Contents

Advertisement

Sequence of Operation

Start-Up / Standby

Prior to start-up, verify that all field-installed sensors
have been installed. This includes a room temperature
sensor (optional) and a discharge air temperature sensor
(standard).

Heat Mode

When the unit or furnace controller calls for heat:
1. The ignition control will check that the pressure
switch for the combustion blower is open.
2. The combustion blower will energize and the
15 second pre-purge begins.
3. The gas valve is energized and the igniter will spark
for up to 10 seconds. If a flame is not sensed during
the trial for ignition, two additional tries will be
attempted before going into lockout for one hour.
4. When a flame is sensed, sparking stops immediately.
The gas valve and combustion blower remain
energized.
5. Ignition
4:1 Electronic Modulation - The burner will light at
100% fire and remain there for 10 seconds. The main
burner gas valve will then modulate from 100% down
to a minimum of 25%, as needed. The combustion
blower will change between high and low speed
to maintain acceptable combustion airflow. If the
high speed pressure switch does not pull in when
required, the furnace will lock out.

Performance Data

Input
Model
(BTU/hr)
50
50,000
75
75,000
100
100,000
125
125,000
150
150,000
175
175,000
200
200,000
225
225,000
250
250,000
275
275,000
10185
300
300,000
11111
325
325,000
12037
350
350,000
12963
400
400,000
14815
20°F
30°F
40°F
1852
1235
926
2778
1852
1389
3704
2469
1852
4630
3086
2315
5556
3704
2778
6481
4321
3241
7407
4938
3704
8333
5556
4167
9259
6173
4630
6790
5093
7407
5556
8025
6019
8642
6481
9877
7407
High Turndown Electronic Modulation - The
furnace controller will ignite the necessary
manifold(s) at 100% for 10 seconds. The main burner
gas valves will then modulate from 100% down to
a minimum of 25% as needed. The combustion
blower will change between high and low speed to
maintain acceptable combustion airflow. If less heat
is needed, a manifold section will be turned off. Each
time a manifold section is initialized, the manifold
section will ignite at 100%.
6. The ignition control constantly monitors the call for
heat, the pressure switch and the burner flame to
assure proper operation.
7. When the unit or furnace controls are satisfied,
the main gas valve is then de-energized and the
combustion blower shuts off following a 30 second
post-purge period.

Recovery from Lockout

If the furnace goes into lockout, the ignition control will
automatically reset after one hour if the thermostat is still
calling for heat. If needed, a manual reset can be
accomplished by either shutting off the power or turning
off the call for heat (turn off the thermostat) for a period
of five seconds.
Supply Air Temperature Rise
50°F
60°F
70°F
CFM
741
617
529
1111
926
794
1481
1235
1058
1852
1543
1323
2222
1852
1587
2593
2160
1852
2963
2469
2116
3333
2778
2381
3704
3086
2646
4074
3395
2910
4444
3704
3175
4815
4012
3439
5185
4321
3704
5926
4938
4233
80°F
90°F
100°F
463
412
370
694
617
556
926
823
741
1157
1029
926
1389
1235
1111
1620
1440
1296
1852
1646
1481
2083
1852
1667
2315
2058
1852
2546
2263
2037
2778
2469
2222
3009
2675
2407
3241
2881
2593
3704
3292
2963

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents