7.1.4.

Statistics

The statistics menu provides information about the lowest measured tempera-
ture, the highest measured temperature and the average measured temperature
for each measuring circuit. The values can be reset.
Condition monitoring – statistics:
7.1.5.

Password reset counter

The password reset counter counts how often the password has been reset by
the user and displays the time when the password was reset. The time given as a
value related to the time since power on.
Condition monitoring – password reset counter:
7.1.6.

Simulation mode

The simulation mode can be used for commissioning or testing. There are two
options in the simulation mode: Simulation of temperature values to test the re-
lay configuration or trip of the relays.
The symbol for simulation mode is displayed in the bottom pane of the display.
The user can navigate through the simulation mode by rotating. To change a
value or a relay position, the according symbol needs to be clicked. For the chan-
nels the temperature can be simulated by clicking and rotating. The changes are
effective immediately. The user can use this mode to test the settings and check
the relay behavior in case of temperature changes. The relays can also be
reached via rotation. Clicking on a relay changes the state immediately.
Condition monitoring – simulation mode: