NOVASCALE Site Preparation Guide Hardware January 2008 BULL CEDOC 357 AVENUE PATTON B.P.20845 49008 ANGERS CEDEX 01 FRANCE REFERENCE 86 A1 87EF 10...
Page 4
Quoting of brand and product names is for information purposes only and does not represent trademark misuse. The information in this document is subject to change without notice. Bull will not be liable for errors contained herein, or for incidental or consequential damages in connection with the use of this material.
Intended Readers This Site Preparation Guide explains how to prepare a Data Processing Center for Bull servers, in compliance with the standards in force. It is to be used by all personnel and trade representatives involved in the site preparation process.
The Customer shall bear the cost of the works to be carried out to attain stipulated safety and continuity of operation requirements. The following web site may be consulted for general site preparation information: http://www.cs.bull.net/aise viii Site Preparation Guide...
Regulatory Specifications and Disclaimers Declaration of the Manufacturer or Importer We hereby certify that this product is in compliance with European Union EMC Directive 2004/108/CE, using standards EN55022 (Class A) and EN55024 and Low Voltage Directive 2006/95/CE, using standard EN60950. The product has been marked with the CE Mark to illustrate its compliance.
Page 12
Federal Communications Commission (FCC) Statement Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
• EN61000-3-2, Limit for Harmonic Current Emissions • EN61000-3-3, Voltage Flicker • FCC Part 15 Class A North America • ICES-003 Issue 3 Class A Bull NovaScale Blade servers also comply with standards: • Japan: IEC 1000-3-2 • Australia / New Zealand: IEC 60950 • Taiwan: BSMI Approval •...
Page 14
Protection against Electrostatic Discharges CMOS (Complementary Metal Oxide Semiconductor) technology is highly sensitive to electrostatic discharges. The use of conductive antistatic flooring is strongly recommended. Maintenance personnel must wear wrist-straps before handling electronic equipment. A ground socket is provided in each cabinet. Shocks and Vibrations The servers comply with standards: IEC 60068-1...
Page 15
• ISO 4871 • ISO 9295 • ISO 9296 • IEC 61260 • IEC 60651 (Bull NovaScale 5xx5 Series & Bull NovaScale 5xx5 Series) • IEC 61672-1 (Bull NovaScale 4000 Series) • IEC 61672-2 (Bull NovaScale 4000 Series) Operating LwAd Acoustical Power •...
• Carry-In Route, on page 1-2 • Unpacking Requirements, on page 1-3 Server Cabinets The servers are delivered rack-mounted and pre-cabled in one or two 19U / 40U cabinets, according to the version chosen. Figure 1. Bull server cabinets General Recommendations...
Delivery Conditions The server is delivered 24 hours in advance of the scheduled installation date. On arrival, the server must be placed, in its packing, in the Computer Room so that it reaches room temperature before powering up (optimum operating temperature = 22° C + 3°...
Unpacking Requirements The cabinet is delivered packed on a pallet with rails for easy unloading. The Data Processing Site manager must set aside the required working area for unpacking, as shown in the following figure. See Appendix A. Specifications for packing size. Figure 2.
Chapter 2. Fitting out the Premises This chapter explains how to plan and fit out your premises to receive your server. It includes the following topics: • Data Processing Center Layout, on page 2-1 • Planning Installation, on page 2-3 •...
For optimum site safety and security, the following figure shows an example of recommended Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Ç Data Processing Center layout.
Planning Installation Installation must be planned so that any changes and / or extensions may be implemented with minimum service disruption. Use the layout grid shown in Figure 7 to plan installation. Each square of the grid represents a standard raised floor panel. CAUTION: It is mandatory for Data Processing Center layout to take the safety of personnel into account.
NovaScale 5xx5 (Remote Maintenance Modem) Partitioned Servers Note: Modem cable connectors differ from country to country. Customers are to provide the RJ11 adapter required to comply with national standards. For further details, please consult your Bull Sales Representative. Site Preparation Guide...
Service Clearance It is mandatory to comply with the service clearance requirements indicated in the following figures: Rear door 100 cm (39.4 in) Server Cabinet Depth * Server/ Wall Server/ Wall Width * 100 cm 100 cm (39.4 in) (39.4 in) 150 cm (59 in) Figure 5.
Electrical / Electromagnetic Interference Generators of electromagnetic interference may adversely affect server operation. The following sources of electrical and / or electromagnetic interference must not be located in the immediate vicinity of the Data Processing Center: • high-voltage lines, • radars, •...
Extinguishing Agents In compliance with APSAD R13. Commonly used extinguishing agents are: • inert gases such as ARGONITE (Argon-based) and INERGEN, • water in the form of sprinklers or sprays (pending certification). CAUTION: It is strongly recommended not to use CO gas (hazard to personnel and to equipment). The use of HALON 1301 gas is prohibited as from January 1 2003.
CAUTION: A raised floor compliant with Standard NF P67 103-1 and 103-2, dated April 1993 is mandatory for the Bull NovaScale Servers. A raised floor allows even distribution of the overall system load and provides a plenum space for cabling and air-conditioning.
Actuators and T–beam section spars Actuators alone Figure 9. Raised floor structure CAUTION: If the air-conditioning unit(s) is (are) placed on brackets in the room, it is mandatory to electrically isolate these brackets from the raised floor slabs, crossbeams, and actuators. Computer Room Ceiling It is extremely important to have sufficient ceiling height so that the premises may be air- conditioned without creating draughts.
• sound-proof walls and partitions. Protection from Sunlight Large glass surfaces must be protected from sunlight. In no event may the Bull NovaScale Server be exposed to direct sunlight. External protections only may be used (coating, canvas curtains or shutter blinds).
Media Storage Room Media may be stored in the Computer Room or in an adjacent room, in which case Computer Room environmental conditions are applicable. The Media Storage Room floor must be designed to support loads of up to 10 kN/m . Media is sensitive to high-power electromagnetic fields.
• Checks and Alarms, see page 3-5 CAUTION: An air-conditioning system, compliant with the requirements of NF X44-101, Class 4 000 000, dated June 1981 and with ISO 7730, is mandatory for the Bull NovaScale Server. Air-Conditioning System Features and Functions...
Distribution Bull NovaScale Servers release high levels of heat and require the installation of a high airflow air-conditioning system. Delivery of air through the raised floor plenum is the most appropriate solution. The air-conditioning specialist must define the number and location of the perforated and / or damper slabs required for correct air distribution.
Circulation The servers are cooled by taking air from inside the room. The following requirements are to be complied with for correct air circulation of air: • raised floor height: > 30 cm, • the raised floor plenum must not be obstructed by oversize pipes or cableways, •...
Page 36
Pollutants There are three types of pollutants: • liquids, • solid particles, • gases. Damage varies according to pollutant type and interaction: corrosion, erosion, mildew, oxidation, etc. Solid particles are abrasive, electrostatic, and absorbent. They generally originate from: • surface crumbling of construction materials used to fit out the Data Processing Center, •...
Checks and Alarms The air-conditioning system is controlled automatically. Variations outside the specified temperature and hygrometry ranges must be transmitted to Customer Service Engineers. Detectors must be installed at the air-conditioning cabinet air inlet and / or in the Computer Room.
Chapter 4. Power Supply This chapter explains power supply requirements for Bull NovaScale Servers. It includes the following topics: • Power Supply, on page 4-1 • Cabling Requirements, on page 4-2 • Grounding Circuit, on page 4-5 • Neutral Power System, on page 4-6 •...
DANGER • To ensure the protection of personnel and equipment, bipolar magneto-thermic circuit breakers must be installed on the phase and neutral wires, in compliance with the safety standards in force. • Power must be exclusively conveyed by copper conductors from the source. Aluminium conductors are prohibited.
Mounting Power Supply Cable Sockets CAUTION: To be performed by a certified electrician only. Tools Required • Multimeter • Phillips screwdriver • Velcro fasteners Europe, Brazil PDU/UPS power cables are equipped with ready-mounted IEC60309 plugs. The Customer is responsible for supplying and installing appropriate sockets for connection to the site power supply.
For PDU/UPS equipped with IEC 60309 plugs. 1. Check that the power supply cable is not live with the multimeter. 2. Carefully guide the power supply cable through the cable inlet at the base of the cabinet. 3. Check that the power supply cable is long enough. 4.
Grounding Circuit The electronic components inside the servers are sensitive to high-frequency electromagnetic interference. To ensure correct hardware operation, high-frequency interference must be limited via an equipotential ground circuit and metallic braid shielded cables. DANGER For the protection of personnel and hardware, it is mandatory for the grounding network to be compliant with Data Processing Center requirements and the standards in force.
Figure 15. Raised floor equipotentiality method Neutral Power System A TN-S neutral point connection system is mandatory for the servers. Constructing a TN-S Neutral Point Connection System The servers are equipped with a high-leakage current switch-mode power supply. The protective conductor (PE) is connected to the neutral conductor at the origin of the installation.
Electricity Power Supply Distribution Interface Panel Data processing equipotential line = flexible multi-strand wire in compliance with standard NFC 15.100. Data processing equipotential bar Raised floor actuator meshing braid Computer and peripherals cab. cab. Main earth plate terminal Measurement bar Figure 16.
Non-Computing Power Supply Prerequisites • Installation of current outlets around the edge of the computing room. • The non-computing power supply (air-conditioners, lighting, etc.) must be separated from the data processing power supply by specific distribution cabinets. Note: The Customer is responsible for supplying the complete electrical installation, from the power delivery station through to the cable outlets at the base of the server cabinet.
Electrical Specifications (power supplies are auto-sensing and auto-ranging) Power consumption 5000 VA (max. per chassis) Thermal dissipation 4706 W / 16067 BTU (max. per chas- sis) Europe Nominal voltage 230 VAC (Phase / Neutral) Voltage range 207 - 244 VAC Frequency 50 Hz United States of America...
NovaScale Blade Chassis (7U) Specifications Dimensions / Weight Height 30.42 cm (12 in, 7U) Width 44.4 cm (17.5 in) Depth 71.1 cm (28.0 in) Weight Chassis + modules + Blades: 108.86 kg (240 lbs) maximum Chassis + modules: 44.91 kg (99 lbs) maximum Electrical Voltage range (VAC) 200 VAC to 240 VAC...
NovaScale Blade 20xx Chassis Specifications Dimensions / Weight Height 30.42 cm (12 in, 7U) Width 44.4 cm (17.5 in) Depth 71.1 cm (28.0 in) Weight Chassis + modules + Blades: 108.86 kg (240 lbs) maximum Chassis + modules: 44.91 kg (99 lbs) maximum Electrical Voltage range (VAC) 200 VAC to 240 VAC...
NovaScale Blade 2020 Server Specifications Dimensions / Weight Height 24.5 cm (9.7 in) Width 2.9 cm (1.14 in) Depth 44.6 cm (17.6 in) Maximum Weight 5.4 kg (12 lbs) Electrical Power Redundant 12 VDC (220 W max.) Voltage range (VDC) 12 VDC Table 5.
NovaScale Blade 2320 Server Specifications Dimensions / Weight Height 24.5 cm (9.7 in) Width 2.9 cm (1.14 in) Depth 44.6 cm (17.6 in) Maximum Weight 5.4 kg (12 lbs) Electrical Power Dual redundant 12 VDC (400 W max.) Voltage range (VDC) 12 VDC Table 8.
NovaScale B280 Server Specifications Dimensions / Weight Height 24.5 cm (9.7 in) Width 5.8 cm (2.28 in) Depth 44.6 cm (17.6 in) Maximum Weight 9.0 kg (20 lbs) Electrical Power Dual redundant 12 VDC (400 W max.) Voltage range (VDC) 12 VDC Table 11.
NovaScale 3005 Series Server Cabinet Specifications The Novascale 3005 Series are delivered rack-mounted in a 19U or 40U cabinet. 40U Cabinet Dimensions / Weight Unpacked Packed Height: 195.0 cm (77.0 in) Height: 200.5 (80.7 in) Width: 65.0 cm (25.6 in) Width: 80.0 cm (31.5 in) Depth:...
Electrical specifications (power supplies are auto-sensing and auto-ranging) Current draw 24 A max. at 240 VAC input per PDU Power consumption 8800 VA (max. 40U cabinet) 5500 VA (max. 19U cabinet) 5700 VA (max. per PDU) Thermal dissipation 1500 VA / 5100 BTU (per Novascale 3045 CPU drawer) Europe Nominal voltage 230 VAC (Phase / Neutral)
Novascale 3025 Server CPU Drawer Specifications Dimensions/Weight Height: 17.6 cm (6.9 inches, 4U) Width: 44.1 cm (17.3 inches) Depth: 76.5 cm (30.1 inches) Weight (base model) 21 kg (46.3 lbs) Weight (max) 48 kg (105.8 lbs) Electrical Power 1760VA Voltage range (VAC) 200 VAC to 240 nominal, autoranging (+6% -10%) 50 to 60 Hz ±...
NovaScale 3045 Server CPU Drawer Specifications Dimensions/Weight Height: 17.6 cm (6.9 inches, 4U) Width: 44.1 cm (17.3 inches) Depth: 76.5 cm (30.1 inches) Weight (base model) 21 kg (46.3 lbs) Weight (max) 48 kg (105.8 lbs) Electrical Power 1760VA Voltage range (VAC) 200 VAC to 240 nominal, autoranging (+6% -10%) 50 to 60 Hz ±...
NovaScale 3045 COMPACT Server CPU Drawer Specifications Dimensions/Weight Height: 8.7 cm (3.4 inches, 2U) Width: 44.1 cm (17.3 inches) Depth: 76.5 cm (30.1 inches) Weight (base model) 21 kg (46.3 lbs) Weight (max) 33 kg (72.8 lbs) Electrical Power 1280VA Voltage range (VAC) 200 VAC to 240 nominal, autoranging (+6% -10%)
Electrical Specifications (power supplies are auto-sensing and auto-ranging) Power consumption 8800 VA (max. 40U cabinet) 5500 VA (max. 19 U cabinet) 5700 VA (max. per PDU-20A) 7300 VA (max. per PDU-0-7-M-32A) Thermal dissipation 1500 W/5100 BTU (per NovaScale 4040) 650 W/2300 BTU (per NovaScale 4020) Europe Nominal voltage...
NovaScale 4020 Server CPU Drawer Specifications Dimensions / Weight Height 8.77 cm (3.5 in, 2U) Width 44.9 cm (17.7 in) Depth 74.7 cm (29.4 in) Weight 30 kg (65 lb) Electrical Power 650 VA Voltage range (VAC) 200 VAC to 240 VAC nominal, autoranging +6%, -10% Frequency 50 to 60 Hz...
NovaScale 4040 Server CPU Drawer Specifications Dimensions / Weight Height 17.53 cm (6.9 in, 4U) Width 44.45 cm (17.5 in) Depth 71.12 cm (28.0 in) Weight 48.08 kg (106 lb) Electrical Power 1500 VA Voltage range (VAC) 200 VAC to 240 VAC nominal, autoranging +6%, -10% Frequency 50 to 60 Hz...
NovaScale R421 Server CPU Drawer Specifications NovaScale R421 Dimensions / Weight Height 4.35 cm (1.75 in, 1U) Width 42.7 cm (16.8 in) Depth 65.0 cm (25.7 in) Weight 15,4 kg (33 lb) Electrical Power (R421) 580 Watts w/PFC (+80% efficiency) Voltage range (VAC) 200 VAC to 240 VAC nominal, autoranging +6%, -10%...
NovaScale R422 Server CPU Drawer Specifications NovaScale R422 Dimensions / Weight Height 4.35 cm (1.75 in, 1U) Width 43.2 cm (17.0 in) Depth 70.4 cm (27.7 in) Weight 18,1 kg (39 lb) Electrical Power (R422) 980 Watts w/PFC (+92% efficiency) Voltage range (VAC) 200 VAC to 240 VAC nominal, autoranging +6%, -10%...
NovaScale Universal R421-E1 Server Drawer Specifications NovaScale Universal R421-E1 Dimensions / Weight Form factor Rack mount 1U drawer Height 4.325 cm (1.703 in) Width without rails 43.0 cm (16.93 in) Width with rails 45.13 cm (17.77 in) Depth without CMA 69.2 cm (27.25 in) Depth with CMA 83.82 cm (33.00 in...
NovaScale Universal R423 Server Drawer Specifications NovaScale Universal R423 Dimensions / Weight Form factor Rack mount 2U drawer Height 8.9 cm (3.5 in) Width 43.7 cm (17.2 in) Depth 64.8 cm (25.5 in) Max. Weight 24.9 kg (55 lb) Electrical Power 700 (1 + 1 redundant) Voltage range (VAC)
NovaScale Universal R425 Server Drawer Specifications NovaScale Universal R425 Dimensions / Weight Form factor Rack mount 3U drawer Height 13.2 cm (5.2 in) Width 45.0 cm (17.7 in) Depth 65.0 cm (25.6 in) Max. Weight 34 kg (75 lb) Electrical Power 800 (1 + 1 redundant) Voltage range (VAC)
Power Cables PDU-0-7-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 ( 3 x 6 mm / #10US) Connector type IEC60309-32A CSS Module AC (20A) 1 per CSS Module Cable type 3 x AWG12 (3 x 4mm / #12US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici-...
Power Cables PDU-0-7-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 ( 3 x 6 mm / #10US) Connector type IEC60309-32A CSS Module AC (20A) 1 per CSS Module Cable type 3 x AWG12 (3 x 4mm / #12US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici-...
Power Cables PDU-2-4-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 ( 3 x 6 mm / #10US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici- nity of the system and to be easily accessible. Each power line must be connected to a se- parate, independent electrical panel and bipolar circuit breaker.
° ° Acoustic Power at Room Temperature +20 C (+68 System Running System Idle Lw(A) 6.3 Bels Lw(A) 6.1 Bels Power Cables PDU-2-4-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 (3 x 6 mm / #10US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici- nity of the system and to be easily accessible.
Power Cables PDU-2-4-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 (3 x 6 mm / #10US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici- nity of the system and to be easily accessible. Each power line must be connected to a se- parate, independent electrical panel and bipolar circuit breaker.
Power Cables PDU-2-4-M-32A AC (32A) 1 per PDU Cable type 3 x AWG10 (3 x 6 mm / #10US) Connector type IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vici- nity of the system and to be easily accessible. Each power line must be connected to a se- parate, independent electrical panel and bipolar circuit breaker.
Auto & Manual Auto & Manual UPS Fail These 4 UPS are compliant with European Power regulation, 230V/2 phases + Neutral. For UPS models to be used in Northern America and other countries, consult your Bull representative. A-37 Specifications and Features...
Page 89
If you require a written reply, please include your complete mailing address below. NAME : Date : COMPANY : ADDRESS : Please give this technical publication remarks form to your BULL representative or mail to: ept. Bull - Documentation D 1 Rue de Provence BP 208...
Page 90
: The latest revision will be provided if no revision number is given. [ _ _ ] NAME: Date: COMPANY: ADDRESS: PHONE: FAX: E-MAIL: For Bull Subsidiaries: Identification: For Bull Affiliated Customers: Customer Code: For Bull Internal Customers: Budgetary Section: For Others: Please ask your Bull representative.