The operating mode can only be displayed via WOLF control accessories with
eBUS capability. For procedures, check the operating instructions of the relevant
accessories.
Operating mode
(display on the BM
programming module)
Status HG
Explanation
Standby
0
Emission test mode
1
Heat demand (heating mode)
3
Heat demand with cycle block
5
Cycle block
6
Frost protection - heating
7
Soft start
8
Cylinder mode
15
Frost protection - cylinder
16
Pump run-on - cylinder
17
Parallel cylinder mode
20
Max. cylinder heating time exceeded
21
Sensor operating mode 2, contact closed
22
Sensor operating mode 3, contact closed
23
3061809_1210
Contractor level parameters
Notes
max.15 min.
see HG09
see A 09
see HG26
for boilers
< + 5 K
see HG19
see A 10
see HG20 , MI 09
see HG24
see HG24
27