Protection Switches / Safety Devices
Reset Protection Switch Refrigerant Compressor
Pre-conditions: The sample gas cooler is correctly decommissioned (notice chapter „Decommissioning").
The sample gas cooler is in a non-explosive area.
DANGER: Explosive Area! The reset of protection switches and safety devices may be
processed exclusively in a non-explosive area considering the instructions of the manufacturer.
DANGER! Supply voltage! Be sure that no part of the sample gas cooler is powered.
Notice the advices of the attached operation instruction: BARTEC Ex d Control Station Type 07-
4C40 01-4000-7D0001/C-05/17-STVT-375605.
Dismantle the right panel and the top panel of the sample gas cooler. Open the encapsulated control unit
(20.0). Reset the device protection switch (F1). Remount accurately all dismantled components.
Encapsulated control unit (20.0)
AGT-PSG GmbH & Co.KG
Errors and printing mistakes excepted
Protection switch refrigerant compressor (F1)
Translation - Manual BCR05 Rev. 06/2017
BCR05
Page 19