External connections

Connecting to LAN
MODBUS
Dig . input
36
Connect the unit to a LAN connection using a standard Ethernet cable fitted with an RJ45
connector.
If a non-prefabricated cable is used, first run sufficient cable length through the house. Mount
the RJ45 connector using the standard Ethernet cable crossover terminology as specified in
T568B.
These mounting instructions can be found on the internet, for example on Wikipedia.
The device will be accessible via the smartphone app (IOS and Android) if your device is con-
nected to the same network via WiFi.
IP address
Description
allocation status
Dynamic IP
If the unit is connected to a router with built-in DHCP server it will
fetch the IP address itself from the router when the unit starts up.
Static IP
With PC Tool it is possible to allocate a static IP address to the device.
MODBUS RTU is only for internal communication between the unit (UVC card) and Dan-
therm's accessories
(HAC, FPC, or HCP11)
Connects via RS485 port
Important! External BMS cannot be connected as Modbus RTU via the RS485 port or via
Dantherm accessories . (HAC, FPC, or HCP11)
Modbus TCP/IP
Controllers in Dantherm's ventilation units have the option of communicating Modbus TCP/
IP via the Ethernet port. This is used for Building Management Systems (BMS) or communica-
tion with smartphone apps.
The unit is fitted with two override inputs, also called digital inputs. These inputs can be used
to select a different fan speed or to activate alarms. The default setting for digital input is:
• Dig. input 1: Ventilation step 2
• Dig. input 2: Ventilation step 4
How it works (example to the right):
• Switch DI1 between pin 2 and 4 will activate input 1
• Switch DI2 between pin 3 and 4 will activate input 2
Dig. input can be used for:
• Ventilation steps from 0 - 4
• Safety shutdown
• High water level sensor.
• Kitchen hood boost
• Other options
Find relevant information and settings in PC Tool under External Control System.
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Installation: External connections
DIG IN
1 2
3
4
1: 12VDC
2: Dig. in 1
3: Dig. in 2
4: GND
DI2
DI1