Warning
WARNING
Caution
34
3
Connect the drain hose to the
drain outlet in use and secure the
connection with a hose clamp.
4
The drain hose must be fitted
with a water trap of min. 100 mm
(option A or B).
Route the hose to a drain and
ensure that it is not exposed
to frost.
Fill the water trap with min.
0.5 L water.
HCV 400/460 only
5
Mount the cable clamp in the
hole in the bottom of the unit
Pass the drain hose through
the cable clamp to form a
water trap.
Material damage (e .g . water damage)
Heat recovery of air with a high moisture content leads to condensation in the heat ex-
changer. Condensate must be led into a drain, as it otherwise may damage the floor under
the unit.
Make sure that the drain hose is installed according to the current operating mode.
Check the water trap regularly, especially during the summer, and make sure it is filled
with water as recommended.
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS