5. TROUBLESHOOTING [Override Operation]
Setting of 
Override Operation
1 2 3 4 5 6 7 8
DIP Switch
ON
SW1
OFF
CN21
CN22
CN9
CN10
CN11
1
5
1
4
1
2
1
2
1
4
SW1
1
8
HC30CPU−
7
1
5
4
1
CN14
CN4
CN6
運転管理
RUNNING CONTROL
警報
故障
ALARM
SHUTDOWN
×
10h
C : 温度 TEMP
E : 故障コー ド ERROR CODE
リ セ ッ ト
エコモー ド
RESET
ECOMODE
表示切替
ドライ ヤー
SELECT
DRYER
22
Power
Supply
②⑥
③⑤
DIP Switch
SW2
ON
(Setting of U-type 
OFF
   Capacity Control System)
1
3 4
CN19
CN18
CN12
1
3
1
3
1
CN7
SW2
1
4
1
7
1
5
1
3
1
CN5
CN3
CN13
Printed Circuit Board
Indicating of
Override Operation
Enabled
5.2.1 Enabling Override Operation
q Press the RESET button.
w Disconnect the power.
e Detach the door (for the 22 kW models) or the
front enclosure panel (for the 37 kW models),
and remove the starter cover.
r Reset the DIP switches (on the printed circuit
board located in the starter/control box) as fol-
lows:
SW1 No. 8: ON (setting of override operation)
SW2 No. 3 & 4: ON & OFF
t Return the door or the front enclosure panel to
their original places.
y Reconnect the power.
The digital monitor displays EE indicating that
the override operation is successfully enabled.
IMPORTANT
Override operation disables the following functions:
– To display the digital monitor (except for EE)
– To turn on (either flashing or not flashing) the ALARM
6
or SHUTDOWN light
– To select a screen by pressing the SELECT button
– To externally output the control signals through the
dry contacts
5.2.2 When Override Operation is not
Allowed
The override operation is not allowed to the fol-
lowing error codes:
E-31: The thermistor TH1 is disconnected or
loosely connected
E-32: The thermistor TH2 is disconnected or
loosely connected
E-41: ROM error (failure of PCB)
E-42: RAM error (failure of PCB)
E-43: E
ROM error (failure of PCB)
2
If this is the case, see pages 23 through 24 to take
corrective measures.
IMPORTANT
For the error code E-33 (failure of pressure sensor):
After enabling an override operation, hold down the
SELECT button and connect the power, and press the
START button. Note that this clears the shutdown
history.
(setting of U-type capacity control)