Chapter 1 Introduction Introduction This manual describes the functions and operations of the SIND Integrator. ● Intended Readers This manual is intended for personnel in charge: • Installation and wiring • Instrumentation and setup of the function • Operation and monitoring of the controller •...
Check the package contents against the list below. If anything is missing or damaged, immediately contact the sales office from which you purchased the product or your nearest Yokogawa representative. • SIND Integrator ....................1 • Integrating ratio label (Parts No.:L4040JA) ............1 •...
The product has a QR Code pasted for efficient plant maintenance work and asset information management. It enables confirming the specifications of purchased products and user’s manuals. For more details, please refer to the following URL. https://www.yokogawa.com/qr-code QR Code is a registered trademark of DENSO WAVE INCORPORATED. IM 01B04M01-02E...
• Yokogawa does not make any warranties regarding the product except those mentioned in the WARRANTY that is provided separately. • Yokogawa assumes no liability to any party for any loss or damage, direct or indirect, caused by the use or any unpredictable defect of the product.
Compatibility with Previous Models Compatibility with style A ● Operation and settings differ from previous model (styles A). Please read this document carefully before operating the product. ● Before installing this product in a system or plant, you must check the jumper settings and parameters described in chapter 5, “Settings.”...
*1: The modular jack conversion adapter (E9786WH) is required for connecting the JHT200 Handy Terminal to the Integrator. The 5 pin-connector type communication cable (F9182EE) and modular jack conversion adapter (E9786WH) is required for connecting the BT200 BRAIN Terminal of YOKOGAWA ELECTRIC Corporation F0201.ai...
Model and Suffix Codes Model Suffix Style Optional Description Codes Suffix Codes SIND Integrator Output Proportional output (*1) Square-root output Indication setter Not provided Provided Style Code Style S (*2) (*3) Option Codes /NHR Without rack case /FBP Power supply fuse bypass /LOCK Power supply plug with lock /WSW...
Chapter 3 Installation Installation For details of the installation procedure and wiring precautions, refer to the instruction manual “Installation of Rack-Mounted Instruments” (IM 1B4F2-01E). IM 01B04M01-02E...
External Wiring (a) All cable ends must furnished with crimp-on type solderless lugs (for 4mm screws). (b) Draw out the internal unit from the rack case. (c) Connect the cables to the correct terminals referring to Figure 3-1. (d) Return the internal unit into the rack case after completing the wiring. (e) Always return the terminal block cover to its original position after completing the wiring.
Connecting the SICD Counter Up to two SICD counters can be connected. (See Figure 3-2.) If the input pulse specifications are the same as the SICD, a third-party electromagnetic counter (24 V DC, 150 mA or less) can also be connected. When a counter other than a SICD is used, connect a diode in parallel with the counter coil to prevent surge voltage.
Connecting a Third-party Counter A third-party counter can be driven by an external power supply, and pulse signals can be generated for output to a computer, for example. 3.3.1 Attaching an External Power Supply Specifications of connectable counter Applied voltage: 30 V DC or less Minimum pulse ON/OFF time: 30 ms(*) each or less *: Long response time (60 ms or less) counters can also be connected by shorting the A and C terminals.
Page 19
3.3 Connecting a Third-party Counter Applicable Cables (1) Signal circuit wiring • Cross-sectional area of the cable conductor: 0.5 to 0.75 mm • Examples of applicable cables: 600 V PVC insulated cable (IV) stranded wires (JIS C 3307); PVC insulated cable for electrical apparatus (KIV) stranded wires (JIS C 3316); Heat-resistant vinyl-insulated cable (UL style 1007) (2) Power supply wiring •...
Chapter 4 Principles of Operation Principle of Operation Input signals are converted to digital data by the A/D conversion circuit after passing through the input processing circuit. The resulting digital data is processed (square root calculation, input scaling, integrating pulse calculation, etc.) by the microcomputer, and turns the output transistor N/OFF by the pulse output circuit.
Page 22
4.1 Principle of Operation Input signals undergo A/D conversion and compensation before being converted to data at INPUT1. On the SIND-20x, input signals also undergo square root calculation. The low input cutoff function is provided for both square root calculation and proportional calculation (w/out square root calculation).
Chapter 5 Setting Setting Items to Confirm before Start of Operation Before you start operation, inspect and confirm the following items: (1) Draw out the internal unit from the rack case, and make sure that the specified fuses are properly mounted in the fuse holders at the rear of the internal unit.
Names of Components The following shows the names of SIND components. Integrating ratio indicator lamp (PPH) Low input cutoff indicator lamp (LCT) Display setter Data digit feed key Parameter selection key Data change key Data setting fix key Tag plate BRAIN connector (w / cover) Key setting enable switch...
Setting Jumper SIND is provided with a Parameter Write Protect (W.P.) jumper. When this jumper is set to ON, changing of parameters by the key switches and Handy Terminal is disabled. “LOC” will be displayed on the display setter if the “→” switch is pressed with the PPH or LCT parameter displayed on the display setter.
*1: The modular jack conversion adapter (E9786WH) is required for connecting the JHT200 Handy Terminal to the Alarm Unit. The 5 pin-connector type communication cable (F9182EE) and modular jack conversion adapter (E9786WH) is required for connecting the BT200 BRAIN Terminal of YOKOGAWA ELECTRIC Corporation. 5.3.1...
Page 27
5.3 Setting of Parameters Indicator out mode is entered if no key switch is Displays previous parameter. operated for 30 minutes when display mode Displays next parameter. parameter is "OFF". Indicator out mode Display mode Display mode is returned to when any key switch is pressed.
Page 28
5.3 Setting of Parameters Setting Parameters Display the desired parameter (integrating ratio or low-cut point), and follow the procedure below to change its setting. (1) Input value (60.00) is displayed at power ON. Press the key. The PPH lamp lights, and the integrating ratio is displayed.
Page 29
5.3 Setting of Parameters Display at Power ON The model with display setter displays REV NO. (revision number of software for SIND for about 2 seconds after power ON. Example of display (REV NO.10) LOC Display When “LOC” is displayed, this indicates that parameter settings cannot be changed. (The Parameter Write Protect jumper on the main board is set to “ON”.) To cancel the “LOC”...
5.3 Setting of Parameters 5.3.3 Setting of Parameters Using Handy Terminal For details of operation and adjusting procedures of JHT200 Handy Terminal, refer to the instruction manual “JHT200 Handy Terminal” (IM 77J50H01-01EN). <Connection> Cable of 5-pin connector type (F9182EE) BRAIN connector JHT200 Handy Terminal Adapter for modular jack (E9786WH) F0504.ai Figure 5-7 Connecting the Handy Terminal...
Parameter List BRAIN communication parameters for SIND are as follows. On the SIND-x04, only the input value can be displayed, and integrating ratio and lowcut point can be displayed and set on the display setter on the front panel. Other, parameters are displayed and set using the Handy Terminal.
Page 32
5.4 Parameter List Parameter Name Symbol Description Setting Range Factory-set Display Value Conditions Setting Parameters SET(I/O) Tag Number 1 TAG NO.1 8 alphanumerics can be Displayed on all entered. Tag Number 2 TAG NO.2 8 alphanumerics can be entered. Comment 1 COMMENT1 8 alphanumerics can be entered.
Page 33
5.4 Parameter List Parameter Name Symbol Description Setting Range Factory-set Display Value Conditions Setting Alarm SET(ALM) Parameters Zero Adjustment ZERO ADJ1 Performs zero adjustment (0% side) on input 1. Displayed on (Input 1) n.nnn V RST n.nnn V INC n.nnn V HINC n.nnn V HDEC n.nnn V DEC n.nnn indicates the current input value.
Chapter 6 Maintenance Maintenance This chapter describes the calibration procedures that can be done in the instrument room or service shop. IM 01B04M01-02E...
Test Equipment For efficient maintenance of this integrator, it is recommended that the user have the following test equipment manufactured by Yokogawa or their equivalent. ● DC Voltage/Current Standard, Yokogawa GS200 or the equivalent……..1 set ● , Yokogawa …................ 1 set...
(c) Turn on SIND with a devices connected, and allow 5 minutes for the system to warm up. 0 0 1 2 3 4 SICD Counter Voltage/Current Standard 2 4 6 Power Yokogawa GS200 or Supply the equivalent F0602.ai Figure 6-2 Wiring Diagram IM 01B04M01-02E...
6.2 Check of I/O 6.2.2 Checking Procedure (a) Set the integrating ratio (PPH) on the SIND integrator to 9000 pph. (b) Apply a voltage of 0 V DC to the input, and reset the integration value on the SICD counter. (c) Apply the input signal in a stepped manner for 400 seconds while monitoring the time, and integrate to 5 V DC.
List of Replaceble Parts Contact YOKOGAWA’s sales office or sales representative when replacing the spare parts. Part Name Part Number Recommended Reference replacement period Fuse S9510VK Approx. 3 years If the fuse breaks or if the replacement period elapses, please have the item replaced.
*2: STATUS error code is to be the addition display (hexadecimal number) when two errors or more occur. *3: If errors continue even when the input is within the range, the input circuit is broken. Contact YOKOGAWA's sales office or sales representative. IM 01B04M01-02E...
Chapter 8 Power Supply Terminal Connections (Option /TB, /A2TB, and /REK) Power Supply Terminal Connections (Options /TB, /A2TB, and /REK) If you specify the terminal block to which the power source is directly connected (option codes: /TB, /A2TB, and /REK), the external wiring to the terminal block is necessary; therefore, drawing out the internal unit requires previous turning off of the power source and disconnection of the wiring from the terminal block.
External View and Names of Components Output Terminal Block Output Terminal Cover Power Fuse Power Terminal Cover Input Terminal Block Power Terminal Power and Ground Terminal connection (Connection screw: M4) Symbol Description Input Terminal Cover + Power supply Ground Figure 8-1 Names of Parts and Power Terminal IM 01B04M01-02E...
Power Supply and Ground Wiring (1) All cable ends must be furnished with crimp-on type solderless lugs (for 4 mm screws). (2) Examples of applicable cables: Cross-sectional area of the cable conductor: 2.0 mm For the power supply, use cable having a cross-sectional area of at least 1.25 mm Applicable cable: 600 V vinyle insulated cable (IV) stranded wires, conforming to JIS C3307.
(SIND-04), input indication can be displayed and integrating ratio and low input cut off can be displayed / set on the front panel. The BT200 BRAIN Terminal of YOKOGAWA Electric Corporation can also be connected. n MOUNTING AND APPEARANCE...
Page 53
: IM 01B04M01-02E Jul. 2002/7th Renewal Mar. 2003/8th Correct May 2004/9th Change of the company name. Oct 2019/10th Change of the style number. Written by Yokogawa Electric Corporation Published by Yokogawa Electric Corporation 2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN...
Page 54
3F Tower D Cartelo Crocodile Building, No.568 West Tianshan Road, Shanghai 200335, CHINA Phone : 86-21-62396262 Fax : 86-21-62387866 YOKOGAWA ELECTRIC KOREA CO., LTD. (Yokogawa B/D, Yangpyeong-dong 4-Ga), 21, Seonyu-ro 45-gil, Yeongdeungpo-gu, Seoul, 07209, KOREA Phone : 82-2-2628-6000 Fax : 82-2-2628-6400 YOKOGAWA ENGINEERING ASIA PTE. LTD.