Restrictions of the max. ambient temperature specified with regard to the installation altitude
Installation altitude
-1 000 to 2 000 m
2 000 to 3 000 m
3 000 to 4 000 m
4 000 to 5 000 m
Base value for the application of the derating factor is the maximum permissible ambient tempera-
1)
ture in °C for 2 000 m
Note
• Linear interpolation between altitudes is permissible.
• The derating factors compensate for the decreasing cooling effect of air at higher altitudes
due to lower density.
• Note the mounting position of the respective module in the technical specifications. The
basis is the standard IEC 61131-2:2017.
• Make sure that the power supplies you use are also rated for altitudes > 2 000 m.
• The "Safety-related shutdown of standard modules" function, as described in the Internet
(https://support.industry.siemens.com/cs/ww/en/view/39198632), is only approved up to
a maximum of 2 000 m.
Product information on the documentation of the ET 200SP distributed I/O system
Product Information, 02/2021, A5E03799595-BG
Using ET 200SP higher than 2 000 m above sea level.
Derating factor for ambient temperature
1.0
0.9
0.8
0.7