Installation, Maintenance & Troubleshooting guide | Version 01
LMR-A: Bypass mode
1A : Keep the LMR-A in Bypass mode.
1B
: Switch ON the 3-Phase incoming main supply.
(*Customer may switch ON the starter directly after switching ON the 3 phase incoming supply irresepctive
of Blinking status as there is only indication for incoming supply faults and no Protection in Byapass mode.)
1C : Amber LED will start blinking for a period of min 0.5 min.
1D : 0.5 min is the default setting which can vary from min 0.5 min to max.5min.
1E
: After the ON-delay duration, amber LED will ON continously indicating that the incoming supply is
healthy(Assuming incoming supply is healthy).
1F
: Press the green push putton for switching ON the starter.
1G : Starter gets switched ON.
1H : Press the red push button for switching OFF the starter.
1I
: Starter gets switched OFF.
1J
: Amber LED indication remains continous ON.
1K : Switch OFF the 3-phase incoming main supply.
1L
: Amber LED indication gets turned OFF indicating that there is no incoming main supply.
11