Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Description
Page
Display
Detail
Display
Display/detail
0
Option
SEG7
Set to Enable BLDC Fan and
Description
Page
Display
Detail
Display
Display/detail
1
SEG2
SEG3
Mode
-
Detail
Display
2
-
SEG8
SEG9
Set BLDC Fan Speed to High
Modulating Valve
Detail
Signal voltage
Display
Modulating
BLDC Fan
Valve
0
Disuse
Disuse
0
1
Use
Disuse
1
2
Disuse
Use
2
3
4
5
6
7
8
3
Use
Use
9
A
B
C
D
E
SEG4 (*1)
Fan control when Thermo Off
Detail
Minimal
Minimal
Fan stop
fan
when
Detail
Display
operation
operation
Cool/Heat
when Heat
when Cool
Thermo
Thermo
Thermo
Off
Off
0
Disuse
Disuse
Disuse
1
Enable
-
2
Disuse
Enable
Disuse
3
Enable
-
4
Disuse
Disuse
Enable
5
Enable
-
6
Disuse
Enable Enable
7
Enable
-
SEG10
Set BLDC Fan Speed to Mid
Signal voltage = 5.0 + β
= 7.5 + α
Display
α (V)
β (V)
0
0
0
0.3
1
0.3
0.7
2
0.7
1
3
1
1.4
4
1.4
1.7
5
1.7
2.1
6
2.1
2.5
7
2.5
-0.3
8
-0.3
-0.7
9
-0.7
-1
A
-1
-1.4
B
-1.4
-1.7
C
-1.7
-2.1
D
-2.1
-2.5
E
-2.5
SEG5
SEG6
Use of central control
fan
Display
Detail
Display
Off
0
Disuse
-
-
1
Enable
-
-
SEG11 (*2)
SEG12
Set BLDC Fan Speed
to Low
Signal
voltage =
Display
Display
2.5 + γ
γ (V)
0
0
1
0.3
2
0.7
3
1
4
1.4
5
1.7
6
2.1
7
2.5
8
-0.3
9
-0.7
A
-1
B
-1.4
C
-1.7
D
-2.1
E
-2.4
-
Detail
-
-