Insulation supports
Size
M6
M8
M10
M12
Cable lugs
Size
M8
M10
M12
Cooling and degrees of protection
Planning the cooling
■
When you plan the cooling of the cabinet:
• make sure that the ventilation of the installation site is sufficient so that the cooling air
flow and ambient temperature requirements of the module are met (see the hardware
manual)
• leave enough free space around the components to ensure sufficient cooling. Observe
the minimum clearances given for each component. For the module specific free space
requirements, see the respective hardware and cabinet installation manuals.
Air-cooled drive systems
■
Air inlets and outlets
Equip the air inlets and outlets with gratings that:
• are large enough to allow sufficient air flow in and out of the cabinet (critical for correct
cooling of the module)
• guide the air flow
• protect against contact
• prevent water splashes from entering the cabinet
• ensure adequate protection against flames or pressure blast originating from inside the
cabinet in case of arc flash or similar failure.
The drawing below shows two typical cabinet cooling solutions. The air inlet is at the bottom
of the cabinet. The outlet is on the roof or on the upper part of the door if room height is
limited.
Generic cabinet planning instructions 43
Max. torque
5 N·m (44 lbf·in)
9 N·m (6.6 lbf·ft)
18 N·m (13.3 lbf·ft)
31 N·m (23 lbf·ft)
Max. torque
15 N·m (11 lbf·ft)
32 N·m (23.5 lbf·ft)
50 N·m (37 lbf·ft)
Strength class
8.8
8.8
8.8
8.8
Strength class
8.8
8.8
8.8